APPROVED EQUAL. When the technical specifications call for a brand name, manufacturer, make, model, or vendor catalog number with acceptance of APPROVED EQUAL, it shall be for the purpose of establishing a level of quality and features desired and acceptable to the City. In such cases, the City will be receptive to any unit that would be considered by qualified City personnel as an approved equal. In that the specified make and model represent a level of quality and features desired by the City, the Bidder must state clearly in the bid any variance from those specifications. It is the Bidder’s responsibility to provide adequate information, in the bid, to enable the City to ensure that the bid meets the required criteria. If adequate information is not submitted with the bid, it may be rejected. The City will be the sole judge in determining if the item bid qualifies as an approved equal.
APPROVED EQUAL. Materials: a. One (1) or two (2) component. b. Meet ASTM C920.
APPROVED EQUAL. Type 2: a. Type: flexible sleeve type.
APPROVED EQUAL. 2-inches and larger: a. Cla-Val. b. Febco.
APPROVED EQUAL. C. Drip-Proof Motors: Unless otherwise indicated, drip-proof motors shall have Class B insulation with a service factor of 1. D. Totally Enclosed Fan Cooled Motors (TEFC): 1.
APPROVED EQUAL. Identical to the severe duty motor except that it will be designed to comply with the minimum nameplate efficiency in Table A. The preferred motor is 4-pole 1800 RPM. Table A, Minimum Nameplate Efficiency NEMA MG-1 Table 12-12 and 20-B Speed, RPM ▇▇▇▇ ▇▇▇▇ ▇▇▇▇ Horsepower 6-Pole 4-Pole 2-Pole 1/2 3/4 1 80.0 82.5 74.0 1.5 85.5 84.0 81.5 2 86.5 84.0 82.5 3 87.5 87.5 84.0 5 87.5 87.5 86.5 7.5 89.5 90.2 87.5 10 89.5 90.2 88.5 15 90.2 91.0 89.5 20 90.2 91.7 89.5 25 91.7 92.4 90.2 30 91.7 92.4 90.2 40 93.0 93.0 91.0 50 93.0 93.6 91.7 60 93.6 94.1 92.4 75 93.6 94.5 92.4 100 94.1 94.5 93.0 125 94.1 94.5 94.1 150 95.0 95.0 95.1 200 95.0 96.4 94.5 250 95.0 96.4 95.0 300 - 96.4 95.0 350 - 96.4 95.8 400 95.0 96.4 95.0 450 95.0 95.4 95.0 500 95.0 96.4 95.0
APPROVED EQUAL. 2. Where the term nonshrink grout or cementitious grout is used in the ontext of details and specifications for equipment mounting, it shall mean Cementitious Nonshrink Grout. Training and quality control by the grout manufacturer's technical representative is not required for rigid equipment mounts installed with cementitious non-shrink grout. May 2017 C01025C17 LARGE PUMP AND Georgetown Wet Weather Treatment Station 11045 - 6 RECIPROCATING EQUIPMENT MOUNTING
APPROVED EQUAL. May 2017 C01025C17 Georgetown Wet Weather Treatment Station 15111 - 2 CUSHIONED SWING CHECK VALVES
APPROVED EQUAL. Direct-discharge check valve (slip-on connection): 1. Provided with 2 stainless steel clamps for attaching the valve to the pipe outside diameter.
APPROVED EQUAL. Shall have Class F insulation with a service factor of 1.15.