Automatic Sprinkler System Sample Clauses

POPULAR SAMPLE Copied 1 times
Automatic Sprinkler System. Landlord agrees to maintain the Automatic Sprinkler System to conform with the requirements of the Utah Fire Rating Bureau for grading the building as an Automatic Sprinklered Building. Tenant agrees to repair any damage to this system arising out of its occupancy, ordinary wear and tear excepted, and to hold Landlord free and harmless from damage to or destruction of any and all property resulting from leakage of said Automatic Sprinkler System during the term of this Lease or any extension thereof, or any holdover occupancy.
Automatic Sprinkler System. 11 - 13 12. Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . 13 - 15 13. Heating and Air Conditioning . . . . . . . . . . . . . . . 15 - 18 14. Electrical and Lighting. . . . . . . . . . . . . . . . . . 18 - 20 15. Lessor Work to Lessee Equipment. . . . . . . . . . . . . . 20
Automatic Sprinkler System. Tenant is responsible for upgrading all sprinklers to quick response heads, per current code, if not already installed. Tenant shall contract with Landlord’s contractor at Tenant’s expense for all automatic fire sprinkler system engineering, materials, and installation. Tenant is responsible for the cost of obtaining approvals from the City of Bellevue, Landlord and Landlord’s designated representative(s). Where existing, in previously improved spaces, the automatic sprinkler system in the Leased Premises may be reused at Tenant’s discretion subject to adequate capacity, condition, acceptable location and code requirements. The Leased Premises must remain fully sprinkled at all times. All sprinkler system modifications shall be made in accordance with the current International Building Code (IBC) and all applicable state and local codes. Tenant is required to submit system design for review and approval prior to beginning work. Tenant shall not proceed with any ceiling work until notified of sprinkler rough-in and inspection. Tenant Design & Construction Manual 2014 19 A vertical clearance of eighteen inches (18”) must be maintained from sprinkler heads to any shelf storage or materials that could impair water distribution. Tenant must take note if sprinkler protection is required above the ceilings of the Leased Premises. If it is required, care must be taken in positioning equipment, ducts, and demising walls, so as not to impair the sprinkler distribution. When impairment is unavoidable, sprinkler coverage above the ceiling must be modified to maintain proper coverage, at Tenant’s expense. To assist with sprinkler layout, Tenant’s architect shall dimension all ceiling grid and elements such as lights, speakers, and other ceiling mounted items from building column lines. Slab penetrations shall be core drilled, sleeved, fire-safe, and waterproofed. Tenant shall have all core drill locations approved by Landlord. All materials shall be listed by Underwriter’s Laboratories. All sprinkler heads shall be quick response and manufactured by Reliable Automatic Sprinkler Co., Inc. Building standard sprinkler heads are as follows: Finished Ceilings - Reliable “G4A” concealed, 165 degree, 1/2” orifice, white paint finish or equivalent, SIN: R5415. Any other sprinkler finish must be specified by Tenant’s architect. Impairment of the sprinkler systems requires drain and re-fill procedures to be followed. Please refer to the Fire System Sprinkler Drain and Re-Fill Pr...
Automatic Sprinkler System. Every Building in the Shopping Center shall be either equipped with automatic sprinkler systems which meet all the standards of the Insurance Services Office (or other similar local organization having jurisdiction) or shall be constructed in such a manner as not to adversely affect the fire rating of any other Building in the Shopping Center. The purpose of this Section 4.8 is to allow each Building in the Shopping Center to be fire rated as a separate and distinct unit without deficiency charge.
Automatic Sprinkler System. The building will be fully protected with a supervised wet-pipe automatic sprinkler system. The sprinkler system will be hydraulically calculated. The system will be designed in accordance with USBC requirements, NFPA 13 requirements, and requirements of the agencies having jurisdiction. System will include piping, backflow preventer assembly, water flow alarms, tamper switches, pressure switches, valves, drains, fire department connections, sprinkler heads, tests drain, auxiliary drains, sprinkler drain risers, wet sprinkler alarm valve assemblies with trim, etc. Sprinklers shall be quick-response, ordinary temperature type. Adjustable concealed sprinkler heads with white cover plate shall be provided in finished areas with solid suspended ceilings and semi-recessed sprinklers will be provided in common area spaces with suspended ceiling tile. Low profile ligature & tamper resistant type sprinklers shall be used in patient treatment areas. Upright, brass sprinklers shall be provided in areas with non-finished ceilings, such as mechanical equipment rooms, electrical rooms, janitor closet, etc. Pipe with trade diameters 2” and smaller shall be Schedule 40 with threaded fittings. Pipe with trade diameters greater than 2” shall be Schedule 40 or Schedule 10 with grooved fittings. A post indicator valve (PIV) will be provided on site. This PIV shall be rough brass finished with two 2.5” (National Standard Thread) inlet(s), inlet caps with chains, and a 4-inch pipe connection. The FDC will be labeled “AUTO SPRINK”. The final location of the PIV will be approved by the local Fire Department.
Automatic Sprinkler System. A. Automatic sprinkler system shall be designed hydraulically using the following design criteria per usable square foot of area. 1. Parking Garage and Loading Dock (Dry): 0.25/3250 maximum spacing 130 sq. /sprinkler head. 2. Retail/Function Space: 0.25/2500, maximum spacing 130 sq. ft./sprinkler head. 3. Storage over 14 Feet Height: .25/2500, maximum spacing 130 square feet/sprinkler head. 4. Mechanical Room: .15/1500, maximum spacing 130 sq. ft./sprinkler head. 5. Office (sprinkler risers and main only), Public Spaces, Conference Area. 12/1500 maximum spacing 225 sq. ft./sprinkler head. 6. Kitchen/Server: 0.20/2000 maximum spacing 130 sq.ft./sprinkler head.

Related to Automatic Sprinkler System

  • Sprinkler System TWENTY-SIXTH.--If there now is or shall be installed in said building a "sprinkler system" the Tenant agrees to keep the appliances thereto in the demised premises in repair and good working condition, and if the New York Board of Fire Underwriters or the New York Fire Insurance Exchange or any bureau, department of official of the State or local government requires or recommends that any changes, modifications, alterations or additional sprinkler heads or other equipment be made or supplied by reason of the Tenant's business, or the location of partitions, trade fixtures, or other contents of the demised premises, or if such changes, modifications, alterations, additional sprinkler heads or other equipment in the demised premises are necessary to prevent the imposition of a penalty or charge against the full allowance for a sprinkler system in the fire insurance rate as fixed by said Exchange, or by any Fire Insurance Company, the Tenant will at the Tenant's own expense, promptly made and supply such changes, modifications, alterations, additional sprinkler heads or other equipment. As additional rent hereunder the Tenant will pay to the Landlord, annually in advance, throughout the term $ toward the contract price for sprinkler supervisory service.

  • Sprinklers Subject to any terms, conditions and limitations set forth herein, Landlord shall provide an operative sprinkler system consisting of mains, laterals, and heads “AS IS” on the date of delivery of the Premises to Tenant. Tenant shall pay for piping distribution, drops and relocation of, or additional, sprinkler system heads and Building firehose or firehose valve cabinets, if Tenant’s Plans and/or any applicable Laws necessitate such.

  • HVAC Heating, ventilating and air conditioning.

  • Unbundled Loop Modifications (Line Conditioning 2.5.1 Line Conditioning is defined as routine network modification that BellSouth regularly undertakes to provide xDSL services to its own customers. This may include the removal of any device, from a copper Loop or copper Subloop that may diminish the capability of the Loop or Subloop to deliver high-speed switched wireline telecommunications capability, including xDSL service. Such devices include, load coils, excessive bridged taps, low pass filters, and range extenders. Excessive bridged taps are bridged taps that serves no network design purpose and that are beyond the limits set according to industry standards and/or the BellSouth’s TR 73600 Unbundled Local Loop Technical Specification. 2.5.2 BellSouth will remove load coils only on copper Loops and Subloops that are less than eighteen thousand (18,000) feet in length. 2.5.3 For any copper loop being ordered by NewPhone which has over six thousand (6,000) feet of combined bridged tap will be modified, upon request from NewPhone, so that the loop will have a maximum of six thousand (6,000) feet of bridged tap. This modification will be performed at no additional charge to NewPhone. Loop conditioning orders that require the removal of bridged tap that serves no network design purpose on a copper Loop that will result in a combined total of bridged tap between two thousand five hundred (2,500) and six thousand (6,000) feet will be performed at the rates set forth in Exhibit A. 2.5.4 NewPhone may request removal of any unnecessary and non-excessive bridged tap (bridged tap between zero (0) and two thousand five hundred (2,500) feet which serves no network design purpose), at rates pursuant to BellSouth’s SC Process as mutually agreed to by the Parties. 2.5.5 Rates for ULM are as set forth in Exhibit A. 2.5.6 BellSouth will not modify a Loop in such a way that it no longer meets the technical parameters of the original Loop type (e.g., voice grade, ADSL, etc.) being ordered. 2.5.7 If NewPhone requests ULM on a reserved facility for a new Loop order, BellSouth may perform a pair change and provision a different Loop facility in lieu of the reserved facility with ULM if feasible. The Loop provisioned will meet or exceed specifications of the requested Loop facility as modified. NewPhone will not be charged for ULM if a different Loop is provisioned. For Loops that require a DLR or its equivalent, BellSouth will provide LMU detail of the Loop provisioned. 2.5.8 NewPhone shall request Loop make up information pursuant to this Attachment prior to submitting a service inquiry and/or a LSR for the Loop type that NewPhone desires BellSouth to condition. 2.5.9 When requesting ULM for a Loop that BellSouth has previously provisioned for NewPhone, NewPhone will submit a SI to BellSouth. If a spare Loop facility that meets the Loop modification specifications requested by NewPhone is available at the location for which the ULM was requested, NewPhone will have the option to change the Loop facility to the qualifying spare facility rather than to provide ULM. In the event that BellSouth changes the Loop facility in lieu of providing ULM, NewPhone will not be charged for ULM but will only be charged the service order charges for submitting an order.

  • Heating, Ventilation and Air Conditioning Landlord shall furnish to the Premises heating, ventilation and air-conditioning (“HVAC”) in accordance with the Design Standards set forth in Exhibit E during Ordinary Business Hours. Landlord shall have access to all air-cooling, fan, ventilating and machine rooms and electrical closets and all other mechanical installations of Landlord (collectively, “Mechanical Installations”), and Tenant shall not construct partitions or other obstructions which may interfere with Landlord’s access thereto or the moving of Landlord’s equipment to and from the Mechanical Installations. No Tenant Party shall at any time enter the Mechanical Installations or tamper with, adjust, or otherwise affect such Mechanical Installations. Landlord shall not be responsible if the HVAC System fails to provide cooled or heated air, as the case may be, to the Premises in accordance with the Design Standards by reason of (i) any equipment installed by, for or on behalf of Tenant, which has an electrical load in excess of the average electrical load and human occupancy factors for the HVAC System as designed, or (ii) any rearrangement of partitioning or other Alterations made or performed by, for or on behalf of Tenant. Tenant shall install, if missing, blinds or shades on all windows, which blinds and shades shall be subject to Landlord’s approval, and shall keep all of the operable windows in the Premises closed, and lower the blinds when necessary because of the sun’s position, whenever the HVAC System is in operation or as and when required by any Requirement. Tenant shall cooperate with Landlord and shall abide by the rules and regulations which Landlord may reasonably prescribe for the proper functioning and protection of the HVAC System.