Automatic Transfer Switch. 3.6.1. The automatic transfer switch shall be sized to the maximum capacity of the emergency generator and have an ampere rating equal or greater than the rating of the engine mounted circuit breaker. 3.6.2. Transfer switch shall be complete with a user friendly control interface with a 128 x 63 graphical LCD display and intuitive symbols for ease of operation 3.6.3. Transfer switch shall be complete with LED indicators for transfer switch status. 3.6.4. Transfer switch shall be UL 1008, and CSA approved. 3.6.5. Transfer switch shall be 2 pole with solid neutral 3.6.6. Transfer switch shall be supplied with “in-phase” monitor, and “engine exerciser”. 3.6.7. Standard of Acceptance: ASCO, Series 300 complete with Accessories #11BE, and #22 and #27. 4. Execution