Breaker. Breaker failure protection shall be provided for the 115kV breaker (52-1) that will send direct transfer trip (“DTT”) to Connecting Transmission Owner’s ▇▇▇▇▇▇▇ Road Substation to trip R20 and R50 for failure of the 52-1 breaker (R80). For loss of SF6, the breaker must trip and block close. DTT receive from Connecting Transmission Owner’s ▇▇▇▇▇▇▇ Road Substation will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, R20 or R50 breaker failure, and if both R20 and R50 are open at the ▇▇▇▇▇▇▇ Road Substation. SERVICE AGREEMENT NO. 2591

Appears in 7 contracts

Sources: Interconnection Agreement, Standard Small Generator Interconnection Agreement, Interconnection Agreement

Breaker. Breaker failure protection shall be provided for the 115kV breaker (52-1) that will send direct transfer trip (“DTT”) to Connecting Transmission Owner’s ▇▇▇▇▇▇▇ Road Substation to trip R20 and R50 for failure of the 52-1 breaker (R80). For loss of SF6, the breaker must trip and block close. DTT receive from Connecting Transmission Owner’s ▇▇▇▇▇▇▇ Road Substation will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, R20 or R50 breaker failure, and if both R20 and R50 are open at the ▇▇▇▇▇▇▇ Road Substation. SERVICE AGREEMENT NO. 2591.

Appears in 4 contracts

Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement

Breaker. Breaker failure protection shall be provided for the 115kV breaker (52-1) that will send direct transfer trip (“DTT”) to Connecting Transmission Owner’s ▇▇▇▇▇▇▇ Road Substation to trip R20 and R50 for failure of the 52-1 breaker (R80). For loss of SF6, the breaker must trip and block close. DTT receive from Connecting Transmission Owner’s ▇▇▇▇▇▇▇ Road Substation will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, R20 or R50 breaker failure, and if both R20 and R50 are open at the ▇▇▇▇▇▇▇ Road Substation. 2-2 SERVICE AGREEMENT NO. 2591

Appears in 2 contracts

Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement