Communication System. This section covers the design, installation and placing into service of the plant communication system which shall include commercial telephone system and page/party communication system. The commercial telephone system shall be a microprocessor-based system with a minimum capacity of 15 trunk connections to the telephone company lines in the telephone closet. Conduit is provided by the contractor for circuit installation and terminations by others. Dedicated direct lines (conduit and circuits) shall be installed by -------------------------------------------------------------------------------- EPC - Exhibit B -------------------- TENASKA GEORGIA GENERATION PROJECT Page 109 of 132 -------------------------------------------------------------------------------- the Contractor from the property line (referenced on the Interconnection Drawing in Exhibit B, Attachment I) to the Switchyard Control building, and on into the main control room. Also, a connection for the plant PCS direct dial-up port shall be provided. All phone lines shall be routed in an independent conduit system. The actual location of the telephone communication stations shall be coordinated with Owner during design. At least six lines shall be available for fax machines, modems, or other equipment.