EMS-RTU. The Connecting Transmission Owner will procure and provide the RTU to the Interconnection Customer for installation on the mounting panel. The RTU cabinet is typically 42” H x 30” W x 12” D and shall be wall-mounted with the bottom edge 36” above the floor with a 5-foot clear working space in front of the mounting panel. The Interconnection Customer shall provide a dedicated 10A, 48 VDC or 125 VDC circuit for the RTU from the station battery system for the ▇▇▇▇▇▇ Solar Collector Substation. The Connecting Transmission Owner shall procure and install the Ruggedcom RX1501 gateway required for interfacing the RTU to the Connecting Transmission Owner’s energy management system (“EMS”) network, and will complete all wiring, testing and commissioning of the RTU.