FREQUENCY MEASUREMENTS. The frequency must be measured locally for each Delivery Point unless Virtual Delivery Points. Accuracy of frequency measurements must be better than 10 mHz. The setpoint of frequency is 50,000 Hz and must be aligned with the local controller. The BSP must only install a frequency meter for the Delivery Point with limited energy reservoir that directly delivers the Service. For a Technical Unit used as part of the Energy Management Strategy of a Providing Group which has energy limited reservoirs but is not the Delivery Point with which the Providing Group is delivering the Service the BSP is not obliged to install a frequency meter.
Appears in 2 contracts
Sources: General Framework for Frequency Containment Reserve Service, General Framework for Frequency Containment Reserve Service