IDC PSS/E Base Case. GLDF 1. transmission facilities operated at 100kV and above, in the CA where the Flowgate’s monitored facility(ies) is located and in CAs that are first tier to the CA where the Flowgate’s monitored facility(ies) is located; or 2. transmission facilities operated at 100kV and above within 10 buses from the monitored facility(ies). If any Flowgates with a 3% to 5% distribution factor from Study 2 or Study 4 are impacted by 5% or more from a prior outage condition (Line Outage Distribution Factor (LODF) from this Study 3, the Flowgate will be added to the list of Coordinated Flowgates.