Common use of Joints Clause in Contracts

Joints. 1. Push-On Type: a. Provide push-on-type joints for all buried pipe unless otherwise specified or indicated. b. Joints shall conform to AWWA C200. 2. Flanged: a. Provide certificate of origin for all flanges. b. Provide flanged joints for all interior and exposed exterior pipe except where otherwise specified or indicated. c. Joints shall conform to AWWA C200 and AWWA C207. d. Flanges shall have a pressure rating not less than that required for pipe. Flanges shall be Class D and be drilled ANSI B16.1 Class 125.