Common use of Load Control Clause in Contracts

Load Control. The PCS shall utilize the revenue meter (MWH) to trim the load on gas turbines selected by the operator to match the preselected load (energy) setpoint entered by the operator. The system will continously monitor, project, and adjust the load on the selected gas turbines to maintain a deviation between the setpoint and the actual delivered energy which does not exceed 1.8 MWh, or 0.9% of the Energy Request for a given hour (as defined in the Power Purchase Agreement), which ever is greater.

Appears in 2 contracts

Sources: Engineering, Procurement and Construction Agreement (Tenaska Georgia Partners Lp), Engineering, Procurement and Construction Agreement (Tenaska Georgia Partners Lp)