Main Steam Flow Capacity Test. As part of Unit 6 Performance Testing, a *** will be performed to assure that Unit 6 can achieve this steam flow operating condition on a continuous basis. Although not specifically addressed in ASME PTC 46, the Main Steam Flow Capacity will be verified using the ASME PTC 46 governed Unit 6 Performance Test instrumentation and calibration methods, except where approved by the Owner. • The test duration will be an 8 hour continuous run. • Fuel and sorbent corrections will not be applied unless outside the range of the Agreement specified design range for these materials. • Condenser exhaust pressure will be controlled as close as possible to ***. by operation of the cooling tower fans. Corrections will be made to adjust results to ***. • Equipment will not exceed EPC Agreement (Exhibit A) or Manufacturer ratings. • Spare/redundant equipment shall not be operated, these include, but are not limited to: • Spare hotwell and condensate booster pumps • Spare pulverizer, unless allowed by Steam Generator guarantee • Spare closed cooling water pump and heat exchanger • Spare limestone ball mill • Spare gypsum dewatering train Contractor shall report test results for the *** and the corresponding net electrical output (which is not guaranteed for this test). Net electrical output shall be corrected to Base Performance Conditions for power factor, and wet bulb.