Metering and Communications Equipment. 10.3.1. Edison shall install, own, and maintain revenue quality meters to measure and record real power (▇▇▇▇▇) and reactive power (vars) (collectively, the meet the requirements of the ISO. 10.3.2. Generation located in ▇▇▇▇▇▇ for delivery to the ISO Grid shall be added to such meter data, without compensation for losses. 10.3.3. The ISO-Approved Meters shall be tested by Edison as required by the ISO Tariff. Edison shall notify ▇▇▇▇▇▇ at least 3 business days in advance of any meter test unless required on shorter notice by the ISO. ▇▇▇▇▇▇ shall be afforded the opportunity to be present during any meter test. Edison shall immediately repair, adjust, or replace any meter or associated equipment found to be defective or inaccurate and shall attempt to notify ▇▇▇▇▇▇ of such required work prior to such work. 10.3.4. ▇▇▇▇▇▇ and Edison shall install communications facilities, equipment, and ▇▇▇▇▇▇ municipal boundaries and Wholesale Transmission Load connected to the Transmission System, to exchange data, and for any other purpose as reasonably required to implement the provisions of this Agreement in accordance with Good Utility Practice. 10.3.5. All metering, communications, and data exchanges required to implement this Agreement shall be automated to the greatest extent practical. The Operating Representatives as defined in Section 10.5 shall coordinate standards and specifications for metering and communications equipment as well as any related hardware and software required to implement this Agreement, provided such metering and communications equipment and existing or planned facilities or software, meet all applicable ISO, Western Utility Practice. 10.3.6. ▇▇▇▇▇▇ shall procure, install and maintain, at its sole expense, communications equipment, and any related hardware and software required to be installed on its system in accordance with this Agreement. This obligation shall include without limitation, the maintenance, repair and testing of the ▇▇▇▇▇▇ MGS Communications Facilities in accordance with Attachment C of this Agreement. ▇▇▇▇▇▇ shall reimburse Edison for all reasonable expenses incurred by Edison for any metering and communications equipment and related hardware and software, including any reasonable modifications to existing facilities or software required for Edison to provide service in accordance with this Agreement. Except as provided in Sections 9.3, any additions, replacements or improvements to such Edison facilities shall be recovered in accordance with Sections 13.1 and 17.2.
Appears in 1 contract
Sources: Laguna Bell Vernon Interconnection Service Agreement
Metering and Communications Equipment. 10.3.1. Edison shall install, own, and maintain revenue quality meters to measure and record real power (▇▇▇▇▇) and reactive power (vars) (collectively, the rections at Laguna ▇▇▇▇ and shall meet the requirements of the ISO.
10.3.2. Generation located in ▇▇▇▇▇▇ Vernon for delivery to the ISO Grid shall be added to such meter data, without compensation for losses.
10.3.3. The ISO-Approved Meters shall be tested by Edison as required by the ISO Tariff. Edison shall notify ▇▇▇▇▇▇ Vernon at least 3 business days in advance of any meter test unless required on shorter notice by the ISO. ▇▇▇▇▇▇ Vernon shall be afforded the opportunity to be present during any meter test. Edison shall immediately repair, adjust, or replace any meter or associated equipment found to be defective or inaccurate and shall attempt to notify ▇▇▇▇▇▇ Vernon of such required work prior to such work.
10.3.4. ▇▇▇▇▇▇ Vernon and Edison shall install communications facilities, equipment, and ▇▇▇▇▇▇ software to s Vernon municipal boundaries and Wholesale Transmission Load connected to the Transmission System, to exchange data, and for any other purpose as reasonably required to implement the provisions of this Agreement in accordance with Good Utility Practice.
10.3.5. All metering, communications, and data exchanges required to implement this Agreement shall be automated to the greatest extent practical. The Operating Representatives as defined in Section 10.5 shall coordinate standards and specifications for metering and communications equipment as well as any related hardware and software required to implement this Agreement, provided such metering and communications equipment and any related hardware and software existing or planned facilities or software, meet all applicable ISO, Western Utility Practice.
10.3.6. ▇▇▇▇▇▇ Vernon shall procure, install and maintain, at its sole expense, communications equipment, and any related hardware and software required to be installed on its system in accordance with this Agreement. This obligation shall include without limitation, the maintenance, repair and testing of the ▇▇▇▇▇▇ Vernon MGS Communications Facilities in accordance with Attachment C of this Agreement. ▇▇▇▇▇▇ Vernon shall reimburse Edison for all reasonable expenses incurred by Edison for any metering and communications equipment and related hardware and software, including any reasonable modifications to existing facilities or software required for Edison to provide service in accordance with this Agreement. Except as provided in Sections 9.3, any additions, replacements or improvements to such Edison facilities shall be recovered in accordance with Sections 13.1 and 17.2.
10.4.1. Vernon shall keep Edison informed on a timely basis of changes in Wholesale Transmission Load and cooperate in planning any addition to or upgrade of facilities to accommodate load growth or additions. Vernon shall provide to Edison by September 1 of each year a good faith, but non- binding five year forecast of monthly load requirements and interruptible load.
10.4.2. Edison shall own, operate and maintain all facilities on its side of the Point of Interconnection in accordance with Good Utility Practice. Edison shall operate and maintain protective equipment on its system in accordance with Good Utility Practice.
10.4.3. Vernon shall provide and maintain, at its sole expense, facilities on its side of the Point of Interconnection in accordance with Good Utility Practice. Vernon shall install protective equipment on its system and take any other reasonable measures t
10.4.4. Tariff, and such power factor requires Edison to take corrective actions on its Transmission System, then Edison at its option may install capacitors installation and ongoing ownership costs, provided that Vernon shall first have the opportunity within 120 days after written notice from Edison to installed pursuant to this Section 10.4.4 shall be considered additions or improvements in accordance with Section 17.2. Likewise, if Edison installs power factor correction devices because the power factor associated with the load served through Laguna ▇▇▇▇ excluding the Wholesale Transmission Load requires such corrective action, Edison shall be responsible for 100% of the cost.
10.4.5. Edison shall notify Vernon of any scheduled maintenance to any Transmission System facility and shall cooperate with Vernon in taking any Transmission System facility out of service for scheduled maintenance.
Appears in 1 contract
Sources: Laguna Bell Vernon Interconnection Service Agreement