Over Voltage Ride-Through. The overvoltage protection equipment at the Facility shall be set so that the Facility will meet the following overvoltage ride-through requirements during voltage affecting one or more of the three voltage phases (as described below)("V" is the voltage of any of the three voltage phases at the point of interconnection). [THESE VALUES MAY BE CHANGED BY THE COMPANY UPON COMPLETION OF THE IRS.] 1. 00 pu V < 1.10 pu 1.10 pu V < 1.15 pu
Appears in 2 contracts
Over Voltage Ride-Through. The overvoltage protection equipment at the Facility shall be set so that the Facility will meet the following overvoltage ride-through requirements during voltage affecting one or more of the three voltage phases (as described below)("V" is the voltage of any of the three voltage phases at the point of interconnection). [THESE VALUES MAY BE CHANGED BY THE COMPANY UPON COMPLETION OF THE IRS.]
1. 00 pu s V < 1.10 pu 1.10 pu V < 1.15 puThe Facility remains connected to the Company System.
Appears in 1 contract
Sources: Power Purchase Agreement