Power Quality Requirements. All power quality parameters (i.e., voltage, flicker, frequency, distortion) are specified at the point of common coupling (PCC) unless otherwise stated. The following requirements must be met: 4.4.1. Voltage – the System must be capable of operating within 6% the nominal supply voltage. The Customer shall provide automatic means of disconnecting the System from the City’s electric system within one second if the voltage cannot be maintained within this tolerance.

Appears in 1 contract

Sources: Interconnection Agreement

Power Quality Requirements. All power quality parameters (i.e., voltage, flicker, frequency, distortion) are specified at the point of common coupling (PCC) unless otherwise stated. The following requirements must be met: 4.4.1. Voltage – the System must shall be capable of operating within 6% the nominal supply voltage. The Customer shall provide automatic means normal voltage operating limits of disconnecting the System from 120 volts or other voltage corresponding to the City’s electric system within one second if 's service voltage at the voltage cannot site. This range results in trip points at 105 volts and 133 volts. Response to abnormal voltages should be maintained within this tolerance.as follows:

Appears in 1 contract

Sources: Interconnection Agreement