SCADA. A supervisory control and data acquisition (“SCADA”) system RTU shall be required at the Clear View Solar Collector Substation. The RTU shall provide Connecting Transmission Owner with supervisory trip control of the interconnection breakers and provide telemetry of key operating parameters of the Interconnection Customer’s facility, which shall include but not be limited to the following points list: Analog points: • A, B, C phase current for all interconnecting breakers; • A, B, C phase voltage for all interconnecting breakers; • ▇▇▇▇▇ for interconnecting breakers; • VARS for interconnecting breakers; and • power factor for interconnecting breakers. Digital points: • trip control of 34.5 kV interconnection breaker (for system emergencies);
Appears in 1 contract
Sources: Service Agreement
SCADA. A supervisory control and data acquisition (“SCADA”) system RTU shall be required at the Clear View Solar Collector Substation. The RTU shall provide Connecting Transmission Owner with supervisory trip control of the interconnection breakers and provide telemetry of key operating parameters of the Interconnection Customer’s facility, which shall include but not be limited to the following points list: Analog points: • A, B, C phase current for all interconnecting breakers; • A, B, C phase voltage for all interconnecting breakers; • ▇▇▇▇▇ for interconnecting breakers; • VARS for interconnecting breakers; and • power factor for interconnecting breakers. Digital points: • trip control of 34.5 kV interconnection breaker (for system emergencies);; •