Screens. For interconnection of a proposed Customer-owned renewable generation system to a radial distribution circuit, the aggregated generation, including the proposed Customer- owned renewable generation, on the circuit shall not exceed 15 % of the line section annual peak load as most recently measured at the substation. A line section is that portion of FPL’s electric system connected to a Customer bounded by automatic sectionalizing devices or the end of the distribution line.
Appears in 4 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement