Substation Technical Requirements. The reactors shall be supplied with current transformers incorporated into the bushing insulators, phase side and neutral side, with two (2) 5P20 protection cores, as well as the current transformers in the neutral of the three-phase setup. The reactance and power values and the definitive characteristics of the equipment shall be determined by the CONCESSIONAIRE, as defined, supported, and approved in the POS. Loss levels shall be guaranteed in transformer for permanent load levels of 100%, 75%, and 50% of the rated power. For the reactor, the loss value shall be guaranteed for operation at the rated voltage. The guaranteed values shall meet IEC 60076 or its ANSI/IEEE equivalent.