Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 326 contracts
Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a all power factor within the range of factors over 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) Local Balancing Authority on a comparable basis, in accordance with Good Utility Practice.. The applicable Local Balancing Authority power factor requirements are listed on the Transmission Provider’s website at
Appears in 42 contracts
Sources: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Connecting Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 15 contracts
Sources: Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice.
Appears in 11 contracts
Sources: Small Generator Interconnection Agreement (Sgia), Small Generator Interconnection Agreement (Sgia), Small Generator Interconnection Agreement (Sgia)
Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery deliver at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 6 contracts
Sources: Surplus Large Generator Interconnection Agreement, Surplus Large Generator Interconnection Agreement, Agreement to Amend Surplus Large Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating the Facility to maintain a effective composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, lagging unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 5 contracts
Sources: Standard Interconnection Agreement, Engineering & Procurement Agreement, Standard Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice.
Appears in 5 contracts
Sources: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a all power factor within the range of factors over 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) Local Balancing Authority on a comparable basis, in accordance with Good Utility Practice.. The
Appears in 5 contracts
Sources: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a with dynamic reactive capability over the power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO System Operator or the Interconnecting Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated synchronous (and non-wind non-synchronous generators as specified in Appendix G, Section A.ii.4, to the New York Control Area or Transmission District (as applicableLGIA) generators on a comparable basis, basis and in accordance with Good Utility PracticeOperating Requirements.
Appears in 4 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 3 contracts
Sources: Standard Large Generator Interconnection Agreement (Lgia), Large Generator Interconnection Agreement, Standard Large Generator Interconnection Agreement (Lgia)
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the theConnecting Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 3 contracts
Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 0.90 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 3 contracts
Sources: Standard Generator Interconnection Agreement (Sgia), Standard Generator Interconnection Agreement (Sgia), Standard Generator Interconnection Agreement (Sgia)
Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 3 contracts
Sources: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice.
Appears in 3 contracts
Sources: Small Generator Interconnection Agreement, Small Generator Interconnection Agreement, Small Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a with dynamic reactive capability over the power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO System Operator or the Interconnecting Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated synchronous (and non-wind non- synchronous generators as specified in Appendix G, Section A.ii.4, to the New York Control Area or Transmission District (as applicableLGIA) generators on a comparable basis, basis and in accordance with Good Utility PracticeOperating Requirements.
Appears in 3 contracts
Sources: Small Generator Interconnection Agreement, Service Agreement, Standard Small Generator Interconnection Agreement (Sgia)
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice. The requirements of this paragraph shall not apply to wind generators.
Appears in 3 contracts
Sources: Small Generator Interconnection Agreement (Sgia), Small Generator Interconnection Agreement (Sgia), Small Generator Interconnection Agreement (Sgia)
Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice. The requirements of Appendix G to this LGIA shall apply to wind generators.
Appears in 2 contracts
Sources: Standard Large Generator Interconnection Agreement (Lgia), Standard Large Generator Interconnection Agreement (Lgia)
Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 2 contracts
Sources: Generator Interconnection Agreement, Interim Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.Practice.
Appears in 1 contract
Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects IPA has established different requirements that apply to all similarly situated generators in connecting to the New York Control Area or Transmission District (as applicable) IPP Switchyard on a comparable basis, in accordance with Good Utility Practicecomparablebasis.
Appears in 1 contract
Sources: Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating Qualifying Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice.
Appears in 1 contract
Sources: Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 1 contract
Synchronous Generation. The Interconnection Customer CustomerNYPA shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects interconnectsNYPA has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 1 contract
Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a all power factor within the range of factors over 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) Local Balancing Authority on a comparable basis, in accordance with Good Utility Practice.a
Appears in 1 contract
Sources: Generator Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its designits Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice.
Appears in 1 contract
Synchronous Generation. The Interconnection Customer shall design its Small Generating the Facility to maintain a effective composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, lagging unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice. Interconnection Customer shall design and maintain the plant auxiliary systems to operate safely throughout the entire real and reactive power design range.
Appears in 1 contract
Sources: Standard Interconnection Agreement
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Balancing Authority Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 1 contract
Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery at continuous rated power output at a power factor at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Operating Agent has established different requirements that apply to all similarly situated interconnected generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 1 contract
Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of established byof 0.95 leading to 0.95 lagging, unless the NYISO ConnectingNYISO or the Transmission Owner in on a comparable basis, until NYISOin whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.
Appears in 1 contract