Undervoltage Ride-Through. The Facility (as a whole) will meet the following undervoltage ride-through requirements during low voltage affecting one or more of the three voltage phases ("V" is the voltage of any three voltage phases at the point of interconnection). [THESE VALUES MAY BE CHANGED BY THE COMPANY UPON COMPLETION OF THE IRS.]: V 0.80 pu The Facility remains connected to the Company System. 0.75 pu V ≤ 0.80 pu The Facility may initiate disconnection from the Company System if the voltage remains in this range for more than 2 seconds. 0.00 pu V ≤ 0.75 pu The Facility may initiate disconnection from the Company System if voltage remains in this range for more than 600 milliseconds.
Appears in 1 contract
Sources: Power Purchase Agreement
Undervoltage Ride-Through. The Facility (as a whole) will meet the following undervoltage ride-through requirements during low voltage affecting one or more of the three voltage phases ("V" is the voltage of any three voltage phases at the point of interconnection). [THESE VALUES MAY BE CHANGED BY THE COMPANY UPON COMPLETION OF THE IRS.]: V 0.80 pu The Facility remains connected to the Company System. 0.75 pu V ≤ 0.80 pu The Facility may initiate disconnection from the Company System if the voltage remains SHEET NO. 80.2CF Effective December 30, 2011 in this range for more than 2 seconds. 0.00 pu V ≤ 0.75 pu The Facility may initiate disconnection from the Company System if voltage remains in this range for more than 600 milliseconds.
Appears in 1 contract
Sources: Power Purchase Agreement
Undervoltage Ride-Through. The Facility (as a whole) will meet the following undervoltage ride-through requirements during low voltage affecting one or more of the three voltage phases ("V" is the voltage of any three voltage phases at the point of interconnection). [THESE VALUES MAY BE CHANGED BY THE COMPANY UPON COMPLETION OF THE IRS.]: V ? 0.80 pu The Facility remains connected to the Company System. 0.75 pu s V ≤ 0.80 pu The Facility may initiate disconnection from the Company System if the voltage remains SHEET NO. 94.1CF Effective December 30, 2011 in this range for more than 2 seconds. 0.00 pu s V ≤ 0.75 pu The Facility may initiate disconnection from the Company System if voltage remains in this range for more than 600 milliseconds.
Appears in 1 contract
Sources: Power Purchase Agreement