Antelope Substation. 1. Install dead-end structure, insulators and line drop, as necessary, to terminate the Antelope – Western Antelope Dry Ranch 66 kV Transmission Line. 2. Three (3) voltage transformers with steel pedestal support structures. 3. Install the following relays for the Antelope – Western Antelope Dry Ranch 66 kV Transmission Line a. One GE L90 line current differential relay with dual dedicated digital communication channels to the Small Generating Facility. b. One SEL-311 line current differential relay with dual dedicated digital communication channels to the Small Generating Facility. 4. Install new telecommunication equipment to support the Antelope - Western Antelope Dry Ranch 66 kV Transmission Line protection, SCADA and the Participating TO’s applicable voice and data requirements.
Antelope Substation. Implement the following upgrades at the Antelope 66kV Substation to support interconnection for the Western Antelope Dry Ranch Project and termination of the Antelope - Western Antelope Dry Ranch 66 kV Transmission Line.
Antelope Substation. Equip 220 kV Position 6 with two 220 kV circuit breakers and four sets of 220 kV disconnect switches to terminate the Antelope-Windhub 500 kV line initially energized at 220 kV.
Antelope Substation. Implement the following upgrades at the Antelope 66kV Substation to support interconnection for the Western Antelope Dry Ranch Project and termination of the Antelope - Western Antelope Dry RanchPlainview 66 kV Transmission Line. a. Circuit Breakers – Two (2) 2000 A 40 kA 66 kV circuit breakers b. Disconnect Switches – Four (4) 2000 A 40 kA horizontal-mounted group-operated disconnect switches c. Bay position conductor d. Power System Controls: Modify points on existing RTU to account for new gen-tie
Antelope Substation a. Protection relays to match relays installed at Q628 66 kV Substation b. Three potential transformers c. Power System Controls: Modification of points on existing RTU to account for new system topology
Antelope Substation. Install one set of N60 relays to add the generation to the ▇▇▇▇▇▇▇▇ ▇▇▇▇ ▇▇▇ ▇▇ SPS.
Antelope Substation. Install one (1) set of N60 relays to add the generation to the Northern Area 500 kV SPS.

Related to Antelope Substation

  • Pipelines Developer shall have no interest in the pipeline gathering system, which gathering system shall remain the sole property of Operator or its Affiliates and shall be maintained at their sole cost and expense.

  • Underground Facilities All underground pipelines, conduits, ducts, cables, wires, manholes, vaults, tanks, tunnels, or other such facilities or attachments, and any encasements containing such facilities, including without limitation those that convey electricity, gases, steam, liquid petroleum products, telephone or other communications, cable television, water, wastewater, storm water, other liquids or chemicals, or traffic or other control systems.

  • Interconnection Facilities 4.1.1 The Interconnection Customer shall pay for the cost of the Interconnection Facilities itemized in Attachment 2 of this Agreement. The NYISO, in consultation with the Connecting Transmission Owner, shall provide a best estimate cost, including overheads, for the purchase and construction of its Interconnection Facilities and provide a detailed itemization of such costs. Costs associated with Interconnection Facilities may be shared with other entities that may benefit from such facilities by agreement of the Interconnection Customer, such other entities, the NYISO, and the Connecting Transmission Owner. 4.1.2 The Interconnection Customer shall be responsible for its share of all reasonable expenses, including overheads, associated with (1) owning, operating, maintaining, repairing, and replacing its own Interconnection Facilities, and

  • Access Toll Connecting Trunk Group Architecture 9.2.1 If WCS chooses to subtend a Verizon access Tandem, WCS’s NPA/NXX must be assigned by WCS to subtend the same Verizon access Tandem that a Verizon NPA/NXX serving the same Rate Center Area subtends as identified in the LERG. 9.2.2 WCS shall establish Access Toll Connecting Trunks pursuant to applicable access Tariffs by which it will provide Switched Exchange Access Services to Interexchange Carriers to enable such Interexchange Carriers to originate and terminate traffic to and from WCS’s Customers. 9.2.3 The Access Toll Connecting Trunks shall be two-way trunks. Such trunks shall connect the End Office WCS utilizes to provide Telephone Exchange Service and Switched Exchange Access to its Customers in a given LATA to the access Tandem(s) Verizon utilizes to provide Exchange Access in such LATA. 9.2.4 Access Toll Connecting Trunks shall be used solely for the transmission and routing of Exchange Access to allow WCS’s Customers to connect to or be connected to the interexchange trunks of any Interexchange Carrier which is connected to a Verizon access Tandem.

  • Interconnection 2.1 This section applies to linking with suppliers providing public telecommunications transport networks or services in order to allow the users of one supplier to communicate with users of another supplier and to access services provided by another supplier, where specific commitments are undertaken.