Breaker. Breaker failure protection shall be provided for the 115kV breaker; this protection must trip the Interconnection Customer’s 115kV breaker and send direct transfer trip to Connecting Transmission Owner’s ▇▇▇▇▇▇▇▇ and Corning Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Small Generating Facility’s interrupter fails to interrupt for internal station faults and loss of SF6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Corning and ▇▇▇▇▇▇▇▇ Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, or breaker failure at the Corning and ▇▇▇▇▇▇▇▇ Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 6 contracts
Sources: Standard Small Generator Interconnection Agreement, Service Agreement, Standard Small Generator Interconnection Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breaker; this . This protection must trip the Interconnection Customer’s 115kV breaker appropriate adjacent breakers and send direct transfer trip to Connecting Transmission Owner’s ▇▇▇▇▇▇▇▇ the Eastover and Corning Schaghticoke Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Small Generating FacilityInterconnection Customer’s interrupter fails to interrupt for internal station faults and loss of SERVICE AGREEMENT NO. 2638 SF6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Corning Schaghticoke and ▇▇▇▇▇▇▇▇ Eastover Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, or breaker failure at the Corning Schaghticoke and ▇▇▇▇▇▇▇▇ Eastover Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 4 contracts
Sources: Service Agreement, Service Agreement, Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breakerbreaker R5; this protection must trip the Interconnection Customer’s 115kV breaker and send direct transfer trip DTT to Connecting Transmission Owner’s ▇▇▇▇North ▇▇▇▇ and Corning Hoosick Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Small Generating Facilityfacility’s interrupter fails to interrupt for internal station faults and loss of SF6 condition, the SERVICE AGREEMENT NO. 2756 Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Corning and ▇▇▇▇North ▇▇▇▇ and Hoosick Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, operation or breaker failure at the Corning and ▇▇▇▇North ▇▇▇▇ Substationsand Hoosick substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 3 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breaker; this protection must trip the Interconnection Customer’s 115kV breaker and send direct transfer trip DTT to Connecting Transmission Owner’s ▇▇▇▇▇▇▇▇ the Mohican and Corning Schaghticoke Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Small Generating Facility’s interrupter fails to interrupt for internal station faults and loss of SF6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Corning Mohican and ▇▇▇▇▇▇▇▇ Schaghticoke Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, or breaker failure at the Corning and ▇▇▇▇▇▇▇▇ Mohican or Schaghticoke Substations. The Interconnection Customer shall provide onON/off OFF switches for the DTT schemes.
Appears in 2 contracts
Sources: Standard Small Generator Interconnection Agreement, Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV 46 kV breaker; this . This protection must trip the Interconnection Customer’s 115kV 46 kV breaker and send direct transfer trip DTT to Connecting Transmission Owner’s ▇▇▇▇▇▇▇▇ Inghams and Corning Valley Substations. For loss of SF6SF-6, the breaker must trip and block close. (Note: When the Small Generating Facility’s interrupter fails to interrupt for internal station faults and loss of SF6 SF-6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV 46 kV system for remote backup.) DTT receive from the Corning Inghams and ▇▇▇▇▇▇▇▇ Valley Substations will be required to trip the Interconnection Customer’s 115kV 46 kV circuit breaker for a line relay operation, operation or breaker failure at the Corning Inghams and ▇▇▇▇▇▇▇▇ Valley Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 1 contract
Sources: Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breaker; this . This protection must trip the Interconnection Customer’s 115kV breaker appropriate adjacent breakers and send direct transfer trip to Connecting Transmission Owner’s ▇▇▇▇▇▇▇▇ the Mohican and Corning Battenkill Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Small Generating Facility’s interrupter fails to interrupt for internal station faults and loss of SF6 SF SERVICE AGREEMENT NO. 2720 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Corning Battenkill and ▇▇▇▇▇▇▇▇ Mohican Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, or breaker failure at the Corning Battenkill and ▇▇▇▇▇▇▇▇ Mohican Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 1 contract
Breaker. Breaker failure protection shall be provided for the 115kV 115 kV breaker; this . This protection must trip the Interconnection Customer’s 115kV 115 kV breaker and send direct transfer trip DTT to Connecting Transmission Owner’s ▇Inghams and ▇▇▇▇▇▇▇ and Corning Substations. For loss of SF6SF-6, the breaker must trip and block close. (Note: When the Small Generating Facility’s interrupter fails to interrupt for internal station faults and loss of SF6 SF-6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV 115 kV system for remote backup.) DTT receive from the Corning Inghams and ▇▇▇▇▇▇▇▇ Substations will be required to trip the Interconnection Customer’s 115kV 115 kV circuit breaker for a line relay operation, operation or breaker failure at the Corning Inghams and ▇▇▇▇▇▇▇▇ Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 1 contract
Sources: Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breaker; this . This protection must trip the Interconnection Customer’s 115kV breaker appropriate adjacent breakers and send direct transfer trip to Connecting Transmission Owner’s ▇▇▇▇▇▇▇▇ and Corning SubstationsTiconderoga Substation. For loss of SF6, the breaker must trip and block close. (Note: When the Small Generating Facility’s interrupter fails to interrupt for internal station faults and SERVICE AGREEMENT NO. 2666 loss of SF6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Corning and ▇▇▇▇▇▇▇▇ Substations Ticonderoga Substation will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, or breaker failure at the Corning and ▇▇▇▇▇▇▇▇ Substations(R2). The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 1 contract
Sources: Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breakerbreaker R5; this protection must trip the Interconnection Customer’s 115kV breaker and send direct transfer trip DTT to Connecting Transmission Owner’s ▇▇▇▇North ▇▇▇▇ and Corning Hoosick Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Small Generating Facilityfacility’s interrupter fails to interrupt for internal station faults and loss of SF6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Corning and ▇▇▇▇North ▇▇▇▇ and Hoosick Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, operation or breaker failure at the Corning and ▇▇▇▇North ▇▇▇▇ Substationsand Hoosick substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 1 contract
Sources: Service Agreement