Circuit Planning. Planning shall include locations of copier, microwaves, coffee machines, dishwashers and vending machines. Provide as a minimum, 20‐amp dedicated circuits with isolated grounds to all copy machines. Provide as a minimum a separate 20‐amp circuit for each device. a) Provide as a minimum isolated ground 20‐amp circuits with surge protected receptacles for all main computer hub network equipment and audio‐visual equipment. b) Provide a minimum of a twenty‐five (25%) percent spare capacity above maximum demand for future growth of the electrical system. c) Dedicated isolated‐grounded circuits are not required for computer receptacles. d) Provide a minimum of one (1) 120‐volt duplex receptacle in all building entrance vestibules.

Appears in 6 contracts

Sources: Lease Agreement, Lease Agreement, Lease Agreement

Circuit Planning. Planning shall include locations of copier, microwaves, coffee machines, dishwashers and vending machines. Provide as a minimum, 20‐amp minimum 20-amp dedicated circuits with isolated grounds to all copy machines. Provide as a minimum a separate 20‐amp 20-amp circuit for each device. a) Provide as a minimum isolated ground 20‐amp 20-amp circuits with surge protected receptacles for all main computer hub network equipment and audio‐visual audio-visual equipment. b) Provide a minimum of a twenty‐five twenty-five (25%) percent spare capacity above maximum demand for future growth of the electrical system. c) Dedicated isolated‐grounded isolated-grounded circuits are not required for computer receptacles. d) Provide a minimum of one (1) 120‐volt 120-volt duplex receptacle in all building entrance vestibules.