Common use of Current transformers Clause in Contracts

Current transformers. All CTs for Type 1, 2 and 3 Meters must meet the following criteria: Type of Meter Relevant Standard Minimum Class Accuracy No. of sets Usage 1 IEC 60044-1 0.2s 2 1 set of CTs dedicated to the Main Meter only and 1 set supplying the Check Meters. Check Meter CTs can be used for other purposes providing the overall accuracy requirements in paragraph 2.2 of these TSRs are met 2 IEC 60044-1 0.2s 1 CTs must be dedicated to the CfD Settlement Activities, supplying both Main Meters and Check Meters. An Type of Meter Relevant Standard Minimum Class Accuracy No. of sets Usage additional set of CTs may be fitted for the Check Meter which may also be used for other purposes providing the overall accuracy requirements in paragraph 2.2 of these TSRs are met.

Appears in 1 contract

Sources: Private Network CFD Agreement

Current transformers. 3.3.1 All CTs for Type 1, 2 and 3 Meters must meet the following criteria: Type of Meter Relevant Standard Minimum Class Accuracy No. of sets Usage 1 IEC 60044-1 0.2s 2 1 set of CTs dedicated to the Main Meter only and 1 set supplying the Check Meters. Check Meter CTs can be used for other purposes providing the overall accuracy requirements in paragraph 2.2 of these TSRs are met 2 IEC 60044-1 0.2s 1 CTs must be dedicated to the CfD Settlement Activities, supplying both Main Meters and Check Meters. An Type of Meter Relevant Standard Minimum Class Accuracy No. of sets Usage additional set of CTs may be fitted for the Check Meter which may also be used for other purposes providing the overall accuracy requirements in paragraph 2.2 of these TSRs are met.

Appears in 1 contract

Sources: Private Network CFD Agreement