Common use of Design Basis Clause in Contracts

Design Basis. Electrical conductors will be selected with an insulation level applicable to the system voltage for which they are used and ampacities suitable for the load being served. -------------------------------------------------------------------------------- Proprietary Information Page 13 AES IRONWOOD CONTRACT FINAL ISSUE - OCTOBER 30, 19988 -------------------------------------------------------------------------------- 2x1 501G REFERENCE PLANT APPLICATION HANDBOOK -------------------------------------------------------------------------------- ELECTRICAL ENGINEERING DESIGN CRITERIA -------------------------------------------------------------------------------- Cable Ampacities The maximum ampacities for any cable will depend upon the worst case in which the cable will be routed (tray, conduit, duct, or direct buried). In addition to ampacity, special requirements, such as voltage drop, fault current availability, and environment, will be taken into consideration in sizing of cable. The allowable ampacity of power cables will be in accordance with NEC requirements.

Appears in 3 contracts