Emergency Power System. 1. Provide and install a pad mounted diesel generator set in waterproof enclosure and storage fuel tank sized for minimum 1 day, eight (8) hours, continuous operation at full load. Generator shall be rated for 277/480 volt service. Designed for harmonic non-linear loads. 2. Generator shall serve an emergency distribution panel through a mechanically held, open transition, electrically operated automatic transfer switches. 3. The emergency distribution system shall serve fire pump, fire jockey pump, smoke exhaust fans, elevators, fire alarm system, stairwell, egress, exit lighting. 4. System shall include a remote generator status panel with start-stop controls and load transfer controls tied to the BMS system.