Isolation Device. Member shall install a manual load-break disconnect switch with a clear visible indication of switch position between Cooperative’s electric system and Member’s Generator. The Isolation Device shall be installed as specified in the Interconnection Standard.
Appears in 13 contracts
Sources: Electric Service Agreement, Electric Service Agreement, Electric Service Agreement
Isolation Device. Member shall install a manual load-break disconnect switch with a clear visible indication of switch position between Cooperative’s Company's electric system and Member’s 's Generator. The Isolation Device shall be installed as specified in the Interconnection Standard.
Appears in 6 contracts
Sources: Standard Interconnection Agreement, Interconnection Agreement, Standard Interconnection Agreement
Isolation Device. Member shall install a manual load-break disconnect switch with a clear visible indication of switch position between Cooperative’s electric system and Member’s GeneratorDistributed Resource. The Isolation Device shall be installed as specified in the Interconnection Standard.
Appears in 3 contracts
Sources: Outdoor Lighting Service Agreement, Interconnection Agreement, Interconnection Agreement
Isolation Device. Member shall install a manual load-break disconnect switch with a clear visible indication of switch position between Cooperative’s 's electric system and Member’s 's Generator. The Isolation Device shall be installed as specified in the Interconnection Standard.
Appears in 1 contract
Sources: Interconnection Agreement