Main Service. Power to the building will be via 20.8KV medium voltage service provided in a dual feed configuration from two separate SMUD substations. i. Two double ended 2500/3325 KVA 20.8kV-480/277V, 3ф, 4W unit substations with 4000A secondary bus will be utilized. ii. Two 2000 Amp bus duct will serve the building through stacked electrical rooms located in the core area. iii. The Unit substation will be equipped with an automatic Main-Tie-Main “Open Transition” transfer system. iv. The service capacity of the entire building is approximately 47 W/gsf (23.5 W/gsf at N+1). Tenant loads are as follows:

Appears in 1 contract

Sources: Predevelopment Agreement

Main Service. Power to the building will be via 20.8KV medium voltage service provided in a dual feed configuration from two separate SMUD substations. i. Two One double ended 2500/3325 KVA 20.8kV-480/277V, 3ф, 4W unit substations with 4000A secondary bus will be utilized. ii. Two One 2000 Amp bus duct will serve the building through stacked electrical rooms located in the core area. iii. The Unit substation will be equipped with an automatic Main-Tie-Main “Open Transition” transfer system. iv. The service capacity of the entire building is approximately 47 19 W/gsf (23.5 W/gsf at N+1)gsf. Tenant loads are as follows:

Appears in 1 contract

Sources: Predevelopment Agreement