Common use of Power Distribution Clause in Contracts

Power Distribution. a. Distribution shall be one electrical room for approximately each 19,000 usable square feet. b. A complete shell electrical system is provided in accordance with applicable codes from a 2000 amp, 277/480 volt, 3-phase service to panel boards with circuit breakers and distribution as required to provide power for HVAC equipment, lighting, and convenience outlets. c. Electrical rooms will provide two 120/208 volt panel boards with 75 KVA transformer. Each panel board shall have a 225 amp main breaker and provisions for 42 one pole bolt-on breakers. d. The electrical system and equipment will have a grounding system required by code.

Appears in 1 contract

Sources: Lease Agreement (Transoma Medical Inc)

Power Distribution. a. Distribution shall be one electrical room for approximately each 19,000 usable square feet. b. A complete shell electrical system is provided in accordance with applicable codes from a 2000 amp, 277/480 volt, 3-phase service to panel boards with circuit breakers and distribution as required to provide power for HVAC IIVAC equipment, lighting, and convenience outlets. c. Electrical rooms will provide two 120/208 120/203 volt panel boards with 75 KVA transformer. Each panel board shall have a 225 amp main breaker and provisions for 42 one pole bolt-on breakers. d. The electrical system and equipment .equipment will have a grounding system required by code.

Appears in 1 contract

Sources: Lease Agreement (Harvard Bioscience Inc)