Power Factor Correction Clause Samples

The Power Factor Correction clause requires parties, typically in an energy supply or equipment contract, to maintain or improve the efficiency of electrical power usage by correcting the power factor. This is often achieved by installing devices such as capacitors or synchronous condensers to reduce reactive power and improve the ratio of real power to apparent power in an electrical system. By enforcing this requirement, the clause helps minimize energy losses, reduce utility charges related to poor power factor, and ensure the electrical system operates efficiently and within regulatory or utility standards.
Power Factor Correction. The customer shall provide, at his expense, the necessary power factor corrective equipment to maintain a power factor of at least 90% lagging unless a power factor adjustment is being applied for billing purposes in accordance with appropriate rate schedules. (Continued) -------------------------------------------------------------------------------- Issued: 9/21/84 Issued By: Effective: 9/21/84 ▇▇▇ ▇. ▇▇▇▇▇▇▇ President Advice No.: 231-E -------------------------------------------------------------------------------- EXHIBIT K - 1 of 7 SIERRA PACIFIC POWER COMPANY ▇▇▇ ▇. ▇▇▇▇▇ ▇▇▇▇, Reno, Nevada 3rd Revised P.S.C.N. Sheet ▇▇. ▇▇ ▇▇▇▇▇▇ ▇▇. ▇▇▇▇▇▇▇▇ ▇▇. ▇ Cancelling 2nd Revised P.S.C.N. Sheet No. 47 -------------------------------------------------------------------------------- Rule No. 15 COGENERATORS AND SMALL POWER PRODUCERS (QF'S)
Power Factor Correction. Power factor correction could be required at SPPCo's option on induction generators greater than 100 KVA.
Power Factor Correction. The customer shall provide, at his expense, the necessary power factor corrective equipment to maintain a power factor of at least 90% lagging unless a power factor adjustment is being applied for billing purposes in accordance with appropriate rate schedules. (Continued) Issued: 9/21/84 Issued By: Effective: 9/21/84 ▇▇▇ ▇. ▇▇▇▇▇▇▇ President Advice No: 231-E
Power Factor Correction. Unless otherwise agreed by the Parties, Buyer shall maintain a minimum power factor of .85 at Buyer's Plant, and shall install such power factor correction equipment as may be required for such purpose. Seller shall be responsible for providing reactive power as may be required to compensate for Buyer's reactive power consumption to the extent Buyer operates above such minimum power factor level.
Power Factor Correction. NBU encourages customers to achieve power factor at or above 95%. Where a customer has power factor correction equipment past the NBU point of delivery, all power factor correction equipment shall be three- phase operable. Power factor correction / kVAR balancing shall also be within 10% phase to phase. Allowable leading kVAR may not exceed the lesser of 25% of a customer’s kW peak monthly demand, or 1,000 kVAR total. Failure to switch power factor correction equipment off and/or exceeding allowable leading kVAR may result in disconnection of service.

Related to Power Factor Correction

  • Power Factor The Power Producer shall maintain the Power Factor as per the prevailing GERC regulations and as may be stipulated / specified by GETCO from time to time. The Power Producer shall provide suitable protection devices, so that the Electric Generators could be isolated automatically when grid supply fails. Connectivity criteria like short circuit level (for switchgear), neutral Grounding, fault clearance time, current unbalance (including negative and zero sequence currents), limit of harmonics etc. shall be as per Grid Code.

  • Power Factor Design Criteria (Reactive Power A wind generating plant shall maintain a power factor within the range of 0.95 leading to 0.95 lagging, measured at the Point of Interconnection as defined in this LGIA, if the ISO’s System Reliability Impact Study shows that such a requirement is necessary to ensure safety or reliability. The power factor range standards can be met using, for example without limitation, power electronics designed to supply this level of reactive capability (taking into account any limitations due to voltage level, real power output, etc.) or fixed and switched capacitors if agreed to by the Connecting Transmission Owner for the Transmission District to which the wind generating plant will be interconnected, or a combination of the two. The Developer shall not disable power factor equipment while the wind plant is in operation. Wind plants shall also be able to provide sufficient dynamic voltage support in lieu of the power system stabilizer and automatic voltage regulation at the generator excitation system if the System Reliability Impact Study shows this to be required for system safety or reliability.

  • Power Factor Design Criteria Developer shall design the Large Generating Facility to maintain an effective power delivery at demonstrated maximum net capability at the Point of Interconnection at a power factor within the range established by the Connecting Transmission Owner on a comparable basis, until NYISO has established different requirements that apply to all generators in the New York Control Area on a comparable basis. The Developer shall design and maintain the plant auxiliary systems to operate safely throughout the entire real and reactive power design range. The Connecting Transmission Owner shall not unreasonably restrict or condition the reactive power production or absorption of the Large Generating Facility in accordance with Good Utility Practice.

  • Loop Provisioning Involving Integrated Digital Loop Carriers 2.6.1 Where Freedom has requested an Unbundled Loop and BellSouth uses IDLC systems to provide the local service to the End User and BellSouth has a suitable alternate facility available, BellSouth will make such alternative facilities available to Freedom. If a suitable alternative facility is not available, then to the extent it is technically feasible, BellSouth will implement one of the following alternative arrangements for Freedom (e.g. hairpinning): 1. Roll the circuit(s) from the IDLC to any spare copper that exists to the customer premises. 2. Roll the circuit(s) from the IDLC to an existing DLC that is not integrated. 3. If capacity exists, provide "side-door" porting through the switch. 4. If capacity exists, provide "Digital Access Cross Connect System (DACS)- door" porting (if the IDLC routes through a DACS prior to integration into the switch). 2.6.2 Arrangements 3 and 4 above require the use of a designed circuit. Therefore, non- designed Loops such as the SL1 voice grade and UCL-ND may not be ordered in these cases. 2.6.3 If no alternate facility is available, and upon request from Freedom, and if agreed to by both Parties, BellSouth may utilize its Special Construction (SC) process to determine the additional costs required to provision facilities. Freedom will then have the option of paying the one-time SC rates to place the Loop.

  • Meter Testing Company shall provide at least twenty-four (24) hours' notice to Seller prior to any test it may perform on the revenue meters or metering equipment. Seller shall have the right to have a representative present during each such test. Seller may request, and Company shall perform, if requested, tests in addition to the every fifth-year test and Seller shall pay the cost of such tests. Company may, in its sole discretion, perform tests in addition to the fifth year test and Company shall pay the cost of such tests. If any of the revenue meters or metering equipment is found to be inaccurate at any time, as determined by testing in accordance with this Section 10.2 (Meter Testing), Company shall promptly cause such equipment to be made accurate, and the period of inaccuracy, as well as an estimate for correct meter readings, shall be determined in accordance with Section 10.3 (Corrections).