Common use of Power Quality Clause in Contracts

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.

Appears in 47 contracts

Sources: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement (Gia)

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1-1989, or the applicable superseding electric industry standard standard, shall control.

Appears in 33 contracts

Sources: Standard Large Generator Interconnection Agreement (Lgia), Standard Large Generator Interconnection Agreement (Lgia), Standard Large Generator Interconnection Agreement (Lgia)

Power Quality. Neither A Party’s facilities shall not cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.

Appears in 23 contracts

Sources: Large Generator Interconnection Agreement, Large Generator Interconnection Agreement, Large Generator Interconnection Agreement

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.

Appears in 13 contracts

Sources: Generator Interconnection Agreement (Gia), Generator Interconnection Agreement (Gia), Generator Interconnection Agreement

Power Quality. Neither No Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1-1989, or the applicable superseding electric industry standard standard, shall control.

Appears in 10 contracts

Sources: Generator Interconnection Agreement, Generator Interconnection Agreement, Interim Generator Interconnection Agreement

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.conflict

Appears in 10 contracts

Sources: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1-1989, or the applicable superseding electric industry standard standard, shall control.

Appears in 9 contracts

Sources: Generator Interconnection Agreement, Standard Large Generator Interconnection Agreement, Service Agreement for Wholesale Distribution Service

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.conflict

Appears in 7 contracts

Sources: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989C84. l-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1-1989, or the applicable superseding electric industry standard standard, shall control.

Appears in 5 contracts

Sources: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

Power Quality. Neither No Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1- 1989, or the applicable superseding electric industry standard standard, shall control.

Appears in 4 contracts

Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1-1989, or the applicable superseding electric industry standard standard, shall control.

Appears in 3 contracts

Sources: Standard Large Generator Interconnection Agreement, Large Generator Interconnection Agreement, Standard Large Generator Interconnection Agreement (Lgia)

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.Standard

Appears in 3 contracts

Sources: Surplus Large Generator Interconnection Agreement, Agreement to Amend Surplus Large Generator Interconnection Agreement, Agreement to Amend Surplus Large Generator Interconnection Agreement

Power Quality. Neither No Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.electric

Appears in 2 contracts

Sources: Settlement Agreement, Generator Interconnection Agreement

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.electric

Appears in 2 contracts

Sources: Generator Interconnection Agreement, Generator Interconnection Agreement

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.applicable

Appears in 2 contracts

Sources: Generator Interconnection Agreement, Generator Interconnection Agreement

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.superseding

Appears in 1 contract

Sources: Standard Large Generator Interconnection Agreement (Lgia)

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standardstandard or Applicable Reliability Standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.or any

Appears in 1 contract

Sources: Large Generator Interconnection Agreement

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.

Appears in 1 contract

Sources: Asset Sale Agreement (CMS Energy Corp)

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.industry

Appears in 1 contract

Sources: Standard Large Generator Interconnection Agreement (Lgia)

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor in accordance with IEEE Standard 1453-2011, or any applicable superseding electric industry standard. Neither Party's facilities shall introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519-1992, or any applicable superseding electric industry standard. In the event of a conflict between ANSI IEEE Standard C84.1519-19891992 or applicable superseding standard, IEEE Standard 1453-2011 or applicable superseding standard, and any applicable superseding electric industry standardMPC Generation and Transmission and End Use Interconnection Requirements, the applicable superseding electric industry standard latter shall control.

Appears in 1 contract

Sources: Large Generator Interconnection Agreement (Lgia)

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1-1989, or the applicable superseding electric industry standard standard, shall control.control.‌

Appears in 1 contract

Sources: Qualifying Facility Transmission Interconnection Agreement

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable Arizona Public Service Company APS Contract No. 52023 LGIA (Large Generator Interconnection Agreement) superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1-1989, or the applicable superseding electric industry standard standard, shall control.

Appears in 1 contract

Sources: Interconnection Agreement (Renegy Holdings, Inc.)

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1C84. 1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1-1989, or the applicable superseding electric industry standard standard, shall control.

Appears in 1 contract

Sources: Generator Tie Line Connection and Lease Agreement

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.industry

Appears in 1 contract

Sources: Standard Large Generator Interconnection Agreement (Lgia)

Power Quality. Neither Party’s Party’sthe facilities of Developer nor the facilities of Transmission Owner shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and or any applicable superseding electric industry standard, ANSI Standard C84.1- 1989, or the applicable superseding electric industry standard standard, shall control.

Appears in 1 contract

Sources: Standard Large Generator Interconnection Agreement

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.

Appears in 1 contract

Sources: Generator Interconnection Agreement

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric Original Sheet No. 42 industry standard, the applicable superseding electric industry standard shall control.

Appears in 1 contract

Sources: Large Generator Interconnection Agreement (ITC Holdings Corp.)

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.conflict

Appears in 1 contract

Sources: Standard Large Generator Interconnection Agreement (Lgia)

Power Quality. Neither Party’s facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard or Electric Reliability Organization standard. In the event of a conflict between ANSI standard C84.1-1989, or any applicable superseding electric industry standard or Electric Reliability Organization standard, ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, or the applicable superseding electric industry standard or Electric Reliability Organization standard, shall control.

Appears in 1 contract

Sources: Standard Large Generator Interconnection Agreement (Lgia)

Power Quality. Neither Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined recommended by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI IEEE Standard C84.1-1989519, and or any applicable superseding electric industry standard, the applicable superseding electric industry standard standard, shall control.

Appears in 1 contract

Sources: Interconnection Agreement

Power Quality. Neither No Party’s 's facilities shall cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves as defined by ANSI Standard C84.1-1989, in accordance with IEEE Standard 519, or any applicable superseding electric industry standard. In the event of a conflict between ANSI Standard C84.1-1989, and any applicable superseding electric industry standard, the applicable superseding electric industry standard shall control.between

Appears in 1 contract

Sources: Generator Interconnection Agreement