Common use of Power Transformers Clause in Contracts

Power Transformers. This section covers the engineering, design, fabrication, delivery and installation of main power transformers (MPT) and auxiliary power transformers (APT), as shown on the electrical one-line, Attachment I. The transformers shall be of the outdoor, oil-filled, self and forced air-cooled type dual 55/65 DEG. C rating with supplementary fan cooling. As an alternate to the 4.16kV-480/277 V oil-filled transformers, the Contractor may utilize an open, dry-type power transformer. The main step-up transformers shall be rated such that the top 55 DEG. C rating shall match the turbine-generator output at 30 DEG. C ambient and 0.85 power factor.