System Acceptance Test. 5.4.1 Supplier shall, at no cost to Host, test the System (with respect to the System, a “System Acceptance Test”) to confirm that the System (i) is capable of delivering Solar Services in accordance with the operational requirements that Supplier shall develop and provide to Host (the “System Requirements”) and (ii) meets all requirements established by the Local Distribution Company and any Applicable Law. 5.4.2 Supplier shall notify Host not less than three (3) days prior to the conducting of System Acceptance Test and Host shall have the right, but not the obligation, to be present at and observe the System Acceptance Test, at no cost to Supplier. 5.4.3 If the results of the System Acceptance Test indicate that the System is capable of delivering electricity generated by the System to Host for eight (8) continuous hours using such instruments and meters as have been installed for such purposes and the System has been approved for interconnected operation by the Local Distribution Company, then Supplier shall send a written notice to that effect to Host (a “Completion Notice”), accompanied by a copy of the results of the System Acceptance Test. ARTICLE 6
Appears in 2 contracts
Sources: Commercial Power Purchase Agreement, Commercial Power Purchase Agreement