Interior Partitions. New interior walls shall be constructed of 3-5/8” x 25 Ga. metal studs at 16” O/C with 1/2” gypsum wallboard on both sides. Walls shall extend to 6” above the ceiling grid. Walls surrounding Clean Room and Gowning Room shall extend to the underside of floor deck above.

Appears in 2 contracts

Sources: Lease (Ocular Therapeutix, Inc), Lease Agreement (Ocular Therapeutix, Inc)

Interior Partitions. New interior walls shall be constructed of 3-5/8” x 25 Ga. metal studs at 16” O/C with 1/2” gypsum wallboard on both sides. Walls shall extend to 6” above the ceiling grid. Walls surrounding Clean Room and Gowning Room shall extend to the underside of floor deck above, except full height at large Conference Room.