Power Factor Requirement. The power factor requirement is as follows: Unit #1: consisting of No.1 LP and HP generators The existing 898 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 20 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals. The existing 896 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 20 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals. The existing 3 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least unity to 0.97 lagging measured at the generator’s terminals. The existing 3 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least unity to 0.97 lagging measured at the generator’s terminals. The existing 3 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least unity to 0.97 lagging measured at the generator’s terminals. The existing 3 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least unity to 0.97 lagging measured at the generator’s terminals.

Appears in 2 contracts

Sources: Interconnection Service Agreement, Interconnection Service Agreement