Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Interconnectionexisting 19.9 MW portion of the Customer Facility shall designretain its Customer Facility with theexisting ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the Point of Interconnection.
Appears in 1 contract
Sources: Interconnection Service Agreement
Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Interconnectionexisting 19.9 existing Interconnection Customer’s Customer Facility shall follow the requirements as specified in Schedule F of this ISA. The increase of 20 MW portion of to the Customer Facility associated with this ISA shall designretain its Customer Facility be designed with theexisting the ability to maintain a power factor of at least 0.95 leading 1.0 (unity) to 0.90 lagging measured at the Point of Interconnection.
Appears in 1 contract