Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time. 2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system. 2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system. 2.4 All the equipments connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time. 2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point. 2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc. 2.7 In order to fulfill Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection. 2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 8 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Net Metering Inter Connection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 7 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 5 contracts
Sources: Provisional Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-non- fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 5 contracts
Sources: Interconnection Agreement, Net Metering Inter Connection Agreement, Net Metering Inter Connection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 4 contracts
Sources: Net Metering Inter Connection Agreement, Interconnection Agreement, Interconnection Agreement
Technical and Interconnection Requirements. 2.1 2.1. Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 2.2. Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 2.3. Consumer agrees that in case of non-non availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 2.4. All the equipments connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 2.5. Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 2.6. Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 2.7. In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 2.8. The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 4 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that metering system(s) shall be installed at Solar PV System for recording the solar generation.
2.3 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s Licensee‟s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 2.4 Consumer agrees that in case of non-availability of grida power outage on Discom‟s system, Rooftop Solar Photovoltaic System solar photovoltaic system will disconnect/isolate automatically and his plant will not inject power into the Licensee’s Licensee‟s distribution system.
2.4 2.5 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 2.6 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 2.7 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 2.8 In order to fulfill Distribution Licensee’s Licensee‟s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Consumer‟s Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s Licensee‟s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 2.9 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant Photovoltaic System when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s consumer‟s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 3 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Inter Connection Agreement (Provisional)
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-non availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 3 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that metering system(s) shall be installed at Solar PV System for recording the solar generation.
2.3 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 2.4 Consumer agrees that in case of non-availability of grida power outage on Discom’s system, Rooftop Solar Photovoltaic System photovoltaic system will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 2.5 All the equipments connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 2.6 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 2.7 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 2.8 In order to fulfill Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 2.9 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant Photovoltaic System when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 3 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 3 contracts
Sources: Net Metering Inter Connection Agreement, Net Metering Inter Connection Agreement, Net Metering Inter Connection Agreement
Technical and Interconnection Requirements. 2.1 The Consumer agrees that his Rooftop Solar PV System solar generation plant and Net Metering System net metering system will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System system to Distribution LicenseeDiscom’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee Discom to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grida power outage on Discom’s system, Rooftop Solar Photovoltaic System photovoltaic system will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority Author5ity (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection interconnection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill Distribution LicenseeDiscom’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee Discom that Consumer’s Rooftop Solar Photovoltaic System photovoltaic system either causes damage to and/or produces adverse effects affecting other consumers or Distribution LicenseeDiscom’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System photovoltaic system immediately from the distribution system upon direction from the Distribution Licensee Discom and correct the problem to the satisfaction of distribution licensee at his own expense prior to a reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEIoff. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 2 contracts
Sources: Net Metering Interconnection Agreement, Net Metering Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that metering system(s) shall be installed at Solar PV System for recording the solar generation.
2.3 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 2.4 Consumer agrees that in case of non-availability of grida power outage on Discom’s system, Rooftop Solar Photovoltaic System solar photovoltaic system will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 2.5 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 2.6 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 2.7 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 2.8 In order to fulfill Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 2.9 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant Photovoltaic System when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 2 contracts
Sources: Inter Connection Agreement (Provisional), Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer The eligible consumer agrees that his Rooftop Solar solar PV System Project and Net Metering System net' metering/ bi-directional metering system will confirm conform to the standards and requirements specified in the Policy, following Regulations and Supply Code codes as amended from time to time.
a) Resources) Regulations, 2013 and amendments thereto.
b) Central Electricity Authority (Installation and Operation of Meters) Regulation 2006 and amendments thereto.
c) OERC Distribution (Conditions of Supply) Code, 2004 and amendments thereto.
2.2 Consumer Eligible consumer agrees that he has installed or / will install, prior to connection of Rooftop Solar Photovoltaic System system to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & and maintenance of the distribution system.
2.3 Consumer Eligible consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his a power outage from system the photo voltaic plant will not inject power into the Licensee’s distribution any tribution system and also ensures that automatic isolation or islanding protection of Solar PV system.
2.4 All the equipments equipment connected to the distribution system shall must be compliant with relevant International international (IEEE/IEC) or Indian Standards standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to timeand amendments thereto.
2.5 Consumer Eligible consumer agrees that licensee will specify the interface/inter inter-connection point and metering point.
2.6 Consumer Eligible consumer and licensee agree to comply with the relevant CEA Regulations regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, voltage frequency, flicker etc.,
2.7 In order Due to fulfill Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer eligible consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces ces adverse effects affecting on other consumers or Distribution Licensee’s assets, Consumer eligible consumer will have to disconnect Rooftop Solar Photovoltaic System photovoltaic system immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to a reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 2 contracts
Sources: Net Metering Agreement, Standard Agreement Form for Net Metering/ Bi Directional Metering of Solar Pv Project
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Gross Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-non- fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 1 contract
Technical and Interconnection Requirements. 2.1 2.1. Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 2.2. Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 2.3. Consumer agrees that in case of non-non - availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 2.4. All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 2.5. Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 2.6. Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 2.7. In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 2.8. The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 1 contract
Sources: Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-non- fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so so, decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 1 contract
Sources: Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that metering system(s) shall be installed at Solar PV System for recording the solar generation.
2.3 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 2.4 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 2.5 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 2.6 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 2.7 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 2.8 In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 2.9 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 1 contract
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments equipment connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering pointmeteringpoint.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 1 contract
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 . Consumer agrees that metering system(s) shall be installed at Solar PV System for recording the solar generation. Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 . Consumer agrees that in case of non-availability of grida power outage on Discom’s system, Rooftop Solar Photovoltaic System photovoltaic system will disconnect/isolate automatically and his plant will not inject power into the Licensee’s distribution system.
2.4 . All the equipments connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 totime. Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 . Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 . In order to fulfill Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 . The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant Photovoltaic System when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 1 contract
Sources: Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.
2.2 Consumer agrees that he has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s Licensee‟s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically and his plant will not inject power into the Licensee’s Licensee‟s distribution system.
2.4 All the equipments connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill Distribution Licensee’s Licensee‟s obligation to maintain a safe and reliable distribution system, Consumer agrees that if it is determined by the Distribution Licensee that Consumer’s Consumer‟s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s Licensee‟s assets, Consumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee at his own expense prior to reconnection.
2.8 The consumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant when the grid supply is off if so decided by CEI. The distribution licensee reserves the right to disconnect the consumer’s consumer‟s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 1 contract
Sources: Interconnection Agreement
Technical and Interconnection Requirements. 2.1 Consumer Consumer/Prosumer agrees that his Rooftop his/her Solar PV System and Net Metering System will confirm conform to the standards and requirements specified in the Electricity Rules, Policy, Regulations and Supply Code and Regulations as amended from time to time.
2.2 Consumer Consumer/Prosumer agrees that he he/she has installed or will install, prior to connection of Rooftop Solar Photovoltaic System to Distribution Licensee’s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Distribution Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system.
2.3 Consumer Consumer/Prosumer agrees that in case of non-availability of grid, Rooftop Solar Photovoltaic System will disconnect/isolate automatically automatically, and his his/her plant will not inject power into the Licensee’s distribution system.
2.4 All the equipments connected to the distribution system shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS) and installations of electrical equipments must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 as amended from time to time.
2.5 Consumer Consumer/Prosumer agrees that licensee will specify the interface/inter connection point and metering point.
2.6 Consumer Consumer/Prosumer and licensee agree to comply with the relevant CEA Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc.
2.7 In order to fulfill fulfil Distribution Licensee’s obligation to maintain a safe and reliable distribution system, Consumer Consumer/Prosumer agrees that if it is determined by the Distribution Licensee that Consumer’s Rooftop Solar Photovoltaic System either causes damage to and/or produces adverse effects affecting other consumers or Distribution Licensee’s assets, Consumer Consumer/Prosumer will have to disconnect Rooftop Solar Photovoltaic System immediately from the distribution system upon direction from the Distribution Licensee and correct the problem to the satisfaction of distribution licensee Distribution Licensee at his own expense prior to reconnection.
2.8 The consumer Consumer/Prosumer shall be solely responsible for any accident to human being/animals whatsoever (fatal/non-fatal/departmental/non-departmental) that may occur due to back feeding from the Rooftop Solar plant Plant when the grid supply is off if so decided by CEI. The distribution licensee Distribution Licensee reserves the right to disconnect the consumer’s installation at any time in the event of such exigencies to prevent accident or damage to man and material.
Appears in 1 contract