Thrust Blocks Clause Samples

The Thrust Blocks clause defines the requirements for installing structural supports that counteract the forces generated by fluid pressure in pipelines, particularly at bends, tees, or dead ends. In practice, this clause specifies the materials, dimensions, and placement of concrete or other suitable blocks to ensure that pipes remain securely anchored during operation. By mandating proper installation of thrust blocks, the clause prevents pipe movement or joint separation, thereby maintaining system integrity and safety.
Thrust Blocks. A. All Portland cement concrete shall conform to the provisions of Section 201 of the SSPWC except as herein modified. B. Portland cement concrete shall be composed of Portland cement, fine aggregate, coarse aggregate, and water proportioned and mixed to produce a smooth dense workable mixture. It can be of the ready-mix variety as produced by any reliable ready-mix concrete firm. C. Portland cement, including Portland cement used in precast products, shall be Type V conforming to ASTM C 150. D. Concrete for thrust blocks shall conform to 560-C-3250 per the SSPWC.
Thrust Blocks. A. Concrete thrust blocks shall be provided where necessary to resist system pressure, including at all direction changes, size changes, valves and terminations or at any other points of the system that will result in an unbalanced thrust line for equipment 2-1/2” and larger and as indicated on the Drawings. Thrust blocks shall not obstruct the outlets of fittings which are intended for future connections. Thrust blocks shall be poured against undisturbed earth and in accordance with the Drawings.
Thrust Blocks. All tees, reducers, bends and crosses shall be anchored to prevent movement by providing suitable concrete thrust blocking as shown on the drawings and specified herein, or required by the Engineer. Thrust blocking is required only at vertical to horizontal transitions (pumphouse risers) or where foundation soils are very compressible. Blocking shall be placed between solid undisturbed ground and the fitting to be anchored. The area of bearing on the undisturbed ground in each instance shall be as shown on the drawings. The blocking shall be so placed that the fitting joints will be accessible for repair.
Thrust Blocks. Unless otherwise ordered by the Engineer, concrete Class 25/19 MPa thrust blocks shall be cast as a support for bends, tees and caps and at valves. The size of the thrust will depend on the strength of the soil, the pipe diameter, the working pressure and the type of item to be supported.
Thrust Blocks. 1. Use thrust blocks for fittings on pipe greater than or equal to 3-inch diameter or any diameter rubber gasketed pipe. 2. Use 3,000-PSI concrete. 3. Use 2-mil plastic. 4. Use No. 4 Rebar wrapped or painted with asphalt tar based mastic coating.

Related to Thrust Blocks

  • Porcupine Site Highway 11 and the City of Timmins Thunder Bay and District Toronto/York-Peel

  • Generators Temporary installation of generators, and permanent installation of generators that are placed inside existing non-residential buildings or that occupy an area under 50 square feet behind the building they serve.

  • Floor Load Tenant shall not place a load upon any floor of the Premises that exceeds 50 pounds per square foot “live load”. Landlord reserves the right to reasonably designate the position of all Equipment which Tenant wishes to place within the Premises, and to place limitations on the weight thereof.

  • Loop Provisioning Involving Integrated Digital Loop Carriers 2.6.1 Where Freedom has requested an Unbundled Loop and BellSouth uses IDLC systems to provide the local service to the End User and BellSouth has a suitable alternate facility available, BellSouth will make such alternative facilities available to Freedom. If a suitable alternative facility is not available, then to the extent it is technically feasible, BellSouth will implement one of the following alternative arrangements for Freedom (e.g. hairpinning): 1. Roll the circuit(s) from the IDLC to any spare copper that exists to the customer premises. 2. Roll the circuit(s) from the IDLC to an existing DLC that is not integrated. 3. If capacity exists, provide "side-door" porting through the switch. 4. If capacity exists, provide "Digital Access Cross Connect System (DACS)- door" porting (if the IDLC routes through a DACS prior to integration into the switch). 2.6.2 Arrangements 3 and 4 above require the use of a designed circuit. Therefore, non- designed Loops such as the SL1 voice grade and UCL-ND may not be ordered in these cases. 2.6.3 If no alternate facility is available, and upon request from Freedom, and if agreed to by both Parties, BellSouth may utilize its Special Construction (SC) process to determine the additional costs required to provision facilities. Freedom will then have the option of paying the one-time SC rates to place the Loop.

  • Fences Except for establishment cost incurred by the United States and replacement cost not due to the Landowner’s negligence or malfeasance, all other costs involved in maintenance of fences and similar facilities to exclude livestock are the responsibility of the Landowner. The installation or use of fences which have the effect of preventing wildlife access and use of the Easement Area are prohibited on the Easement Area, easement boundary, or on the Landowner’s land that is immediately adjacent to, and functionally related to, the Easement Area.