Transformers. Dry-type K20 rated transformers will be provided for 120/208 volt panels. 16A-▇▇ ▇▇▇▇▇▇▇▇▇▇▇ ▇▇▇▇▇▇▇▇▇▇▇ ▇▇▇l be 480/277 volt, 3-phase, 4-wire and 120/208 volt, 3-phase, 4-wire with 200% neutrals with provisions for bolt in circuit breakers. Panelboards will be sized for the HVAC 6 watt▇ ▇▇▇ square foot and 2 watt▇ ▇▇▇ square foot for the 277 volt light fixtures and 6 watt▇ ▇▇▇ square foot at for 120/208 volt power. Panelboards will be located in electrical closets on each floor. 16A-08 WIRING DEVICES, OUTLETS AND SWITCHES
Appears in 2 contracts
Sources: Lease Agreement (Unisphere Networks Inc), Lease Agreement (Unisphere Solutions Inc)
Transformers. Dry-type K20 K13 rated transformers will be provided for 120/208 volt panels. 16A-▇▇ ▇▇▇▇▇▇▇▇▇▇▇ ▇▇▇▇▇▇▇▇▇▇▇ ▇▇▇l be 480/277 volt, 3-phase, 4-wire and 120/208 volt, 3-phase, 4-wire with 200% neutrals with provisions for bolt in circuit breakers. Panelboards will be sized for the HVAC 6 watt▇ ▇▇▇ square foot and HVAC, 2 watt▇ ▇▇▇ square foot for the 277 volt light fixtures and 6 watt▇ ▇▇▇ square foot at for 120/208 volt power. Panelboards will be located in electrical closets on each floor. 16A-08 WIRING DEVICES, OUTLETS AND SWITCHES
Appears in 1 contract