FACILITY TESTS Sample Clauses

The FACILITY TESTS clause defines the procedures and requirements for testing a facility or system to ensure it meets specified performance and operational standards before it is accepted by the client or put into service. Typically, this clause outlines the types of tests to be conducted, the responsibilities of each party during testing, and the criteria for passing or failing the tests. For example, it may require the contractor to demonstrate that all equipment operates correctly under normal and peak conditions. The core function of this clause is to verify that the facility is fully functional and compliant with contractual specifications, thereby reducing the risk of defects or operational failures after handover.
FACILITY TESTS. Prior to achieving Commercial Operations and in each Measurement Period, unless waived by Company, Seller shall demonstrate that the Facility satisfies the following: Maintains output provided by the Company through a control setpoint, as measured at the Point of Interconnection, and is able to continuously dispatch the full Contract Capacity (the “Capacity Test”) Demonstrates the charging/discharging requisite to satisfy the performance standard set forth in Section 3(w) (Round Trip Efficiency) of Attachment B (Facility Owned by Seller) (the “RTE Test”) The RTE Test requires measurement ofCharging Energy” at the Point of Interconnection (MWh from the grid) from Facility 0% State of Charge to bring the Facility to a 100% State of Charge, followed by measurement of the MWh delivered to the grid to bring the Facility to a 0% State of Charge. The RTE Test will be conducted concurrently with the Capacity Test. The Capacity Test can only be performed when the Facility is at the lower of: (i) its maximum State of Charge or (ii) 100% State of Charge prior to the start of the Capacity Test and during the Capacity Test the Company Dispatch/Charge allows for continuous dispatch of the Facility to 0% State of Charge with energy delivered to the Point of Interconnection. For the purposes of evaluating the Capacity Test, the “Capacity Ratio” shall be equal to the number, expressed as a percentage, equal to the total MWh delivered to the Point of Interconnection during the Capacity Test, divided by the Contract Capacity. Further, the Capacity Test will be deemed to be “passed” or “satisfied” to the extent the Capacity Ratio is not less than 100% (the “Capacity Performance Metric”). For the purposes of evaluating the RTE Test, the RTE Ratio shall be equal to the number, expressed as a percentage, equal to the total MWh delivered to the Point of Interconnection during the Capacity Test, divided by the “Charging Energy” measured at the Point of Interconnection. For purposes of the RTE Test, the charging cycle shall begin when the Facility is at a 0% State of Charge prior to the commencement of the Capacity Test and the Charging Energy is the amount of energy imported from the grid, as measured at the Point of Interconnection, that brings the Facility to a 100% State of Charge. The formula is RTE Ratio = MWh discharge ÷ MWh charge. The RTE Test will be deemed to have been “passed” or “satisfied” to the extent the RTE Ratio is not less than the performance standard (the “R...
FACILITY TESTS. Contractor shall conduct the Availability Test and Functional Test for the Facility in accordance with Exhibit 25, and when Contractor believes that the Facility can satisfy the Minimum Capacity Level, Contractor shall conduct the Power Plant Controller Test and the Capacity Test in accordance with Exhibit 14B or Exhibit 14C, as applicable. Contractor shall submit a test report for each Facility Test within five (5) Days after the completion thereof, which test report shall include a summary of such Facility Test and the results for such test. Owner and Contractor will negotiate in good faith to agree upon detailed testing procedures that comply with the protocols set forth in Exhibit 14B, Exhibit 14C and Exhibit 25.
FACILITY TESTS. (i) On the Drawdown Date, no LTV Event has occurred which is continuing and the making of the Loan will not cause the occurrence of an LTV Event. (ii) On the Drawdown Date, in the case of a Loan made after the DSCR Commencement Date, either (1) no DSCR Cash Trap Event has occurred which is continuing or (2) if a DSCR Cash Trap Event was continuing prior to such Drawdown Date, the DSCR after giving effect to the making of the Loan would be equal to or greater than the DSCR immediately prior to such Drawdown Date, calculated on a pro forma basis including the contractual cashflows from the related Asset. (iii) On the Drawdown Date, after giving effect to the making of the Loan and related acquisition of Assets, WLFC or the Borrower shall have invested the Minimum Equity Amount in the Assets, as certified by an Authorized Representative of the Borrower. (iv) After giving effect to the making of the Loan and related acquisition of Assets, no Concentration Breach Event shall have occurred and be continuing.
FACILITY TESTS. 98 Section 7.01.

Related to FACILITY TESTS

  • Stability Testing Patheon will conduct stability testing on the Products in accordance with the protocols set out in the Specifications for the separate fees and during the time periods set out in Schedule C. Patheon will not make any changes to these testing protocols without prior written approval from Client. If a confirmed stability test failure occurs, Patheon will notify Client within [***], after which Patheon and Client will jointly determine the proceedings and methods to be undertaken to investigate the cause of the failure, including which party will bear the cost of the investigation. Patheon will not be liable for these costs unless it has failed to perform the Manufacturing Services in accordance with the Specifications and cGMPs. Patheon will give Client all stability test data and results at Client’s request.

  • Acceptance Tests 11.1 If the Contract provides acceptance tests for Goods and/or the result of Services after their completion and/or delivery to the Purchaser, the acceptance shall only be considered as definitive when such tests have demonstrated the compliance of the Goods and/or the result of the Services to the requirements in the Contract. 11.2 Where the Contract provides for an acceptance procedure in the presence of both parties, at the successful completion of such procedure, the Purchaser shall issue the Supplier with an acceptance certificate which shall authorise the Supplier to invoice the Purchaser for any payment due on such acceptance. 11.3 The Purchaser shall at its discretion be entitled to issue and acceptancecertificate with reserves. The Supplier shall be obliged to remedy any non-conformities within the period set out in the acceptance certificate. Any payment which would otherwise have been due on acceptance may be withheld by the Purchaser in whole or part until the non- conformities underlying the reserves have been remedied.

  • Performance Tests Contractor shall perform Performance Tests in accordance with Section 11.2 of the Agreement and Attachment S.

  • Test conditions 6.1.1. The test shall be performed on a flat, dry concrete or asphalt surface affording good adhesion. 6.1.2. The ambient temperature shall be between 0°C and 45°C. 6.1.3. The horizontal visibility range shall allow the target to be observed throughout the test.

  • Test The outer surface of the lamp lenses shall be subjected once or more than once to the action of the sand jet produced as described above. The jet shall be sprayed almost perpendicular to the surface to be tested. The deterioration shall be checked by means of one or more samples of glass placed as a reference near the lenses to be tested. The mixture shall be sprayed until the variation in the diffusion of light on the sample or samples measured by the method described in Appendix 2, is such that: Δ d = (T5 - T4) / T2 ≤ 0.0250 ± 0.0025 Several reference samples may be used to check that the whole surface to be tested has deteriorated homogeneously.