Common use of Interconnection Customer’s Interconnection Facilities Clause in Contracts

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:

Appears in 11 contracts

Sources: Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one-one- line diagram in Attachment 3, the ICIF consist of the following: 1. ▇▇▇▇▇ Solar Collector Substation

Appears in 7 contracts

Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one-line oneline diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2571

Appears in 6 contracts

Sources: Standard Small Generator Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment RTU described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following: 1. Tayandenega Solar Collector Substation

Appears in 5 contracts

Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2638

Appears in 4 contracts

Sources: Service Agreement, Service Agreement, Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one-one- line diagram in Attachment 3, the ICIF consist of the following: 1. ▇▇▇▇▇▇ Road Collector Substation

Appears in 3 contracts

Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIFICIFs”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering metering, remote terminal unit (“RTU”), and telecommunications equipment described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF ICIFs consist of the following:: SERVICE AGREEMENT NO. 2756

Appears in 3 contracts

Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following: 1. Rock District Solar Collector Substation

Appears in 3 contracts

Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2777

Appears in 2 contracts

Sources: Service Agreement, Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment RTU described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:

Appears in 2 contracts

Sources: Service Agreement, Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2662

Appears in 2 contracts

Sources: Service Agreement, Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one-line oneline diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2574

Appears in 2 contracts

Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement

Interconnection Customer’s Interconnection Facilities. The As depicted on the one-line diagram in Attachment 3, the Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:SERVICE AGREEMENT NO. 2673

Appears in 2 contracts

Sources: Interconnection Agreement, Interconnection Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications energy management system and remote terminal unit (“EMS-RTU”) equipment described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:

Appears in 2 contracts

Sources: Service Agreement, Service Agreement

Interconnection Customer’s Interconnection Facilities. The As depicted on the one line diagram in Attachment 3, the Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. As depicted on the one-line diagram in Attachment 3, the The ICIF consist of a collector station (the following:“Little Pond Solar Collector Substation”) and the generator lead line. Each of the Power Electronics FS3190MU inverters contains an integrated transformer that steps up power to

Appears in 2 contracts

Sources: Service Agreement, Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF consist consists of the following:

Appears in 2 contracts

Sources: Service Agreement, Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:

Appears in 1 contract

Sources: Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except . The ICIF will be located on property owned or leased by the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C belowInterconnection Customer. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:

Appears in 1 contract

Sources: Service Agreement

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIFICIFs”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering metering, remote terminal unit (“RTU”), and telecommunications equipment described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF ICIFs consist of the following: 1. Hawthorn Solar Collector Substation

Appears in 1 contract

Sources: Service Agreement