Control Panels Clause Samples
Control Panels. This section covers the design, fabrication and installation of floor and wall mounted control panels for the project.
6.1. Panels shall be of all welded steel construction. Exterior surfaces shall be smooth and free of defects and imperfections. All welds shall be ground smooth. Exposed edges, corners and edges of cutouts shall be smooth and rounded. Control panel doors shall be provided with full length piano type hinges and three point latching system fasteners with stainless steel handles. the locks shall be keyed alike. -------------------------------------------------------------------------------- EPC - Exhibit B -------------------- TENASKA GEORGIA GENERATION PROJECT Page 131 of 132 -------------------------------------------------------------------------------- Braces and stiffening members shall be provided as required to prevent any panel distortion. Braces and stiffeners shall not interfere with instrument locations.
Control Panels a. Visually inspect the control panel, relay contacts and connectors
b. Insure all lamps and switches are properly labeled and readable
c. Clean the control panel, all relays and all connections
d. Check the tightness of all connections
e. Activate each zone and test proper operation of:
(1) Zone Lights
(2) Trouble Lamps, Switches and Devices
(3) Output to Remote Annunciators
(4) City Connection
(5) Auxiliary Functions
f. Adjust the control components in accordance with the manufacturer’s specifications
g. Insure control panel is fully functional in regular mode and emergency power mode
h. Insure operating instructions are conspicuous
Control Panels. 1. The control panels to be provided for the Multi-rake Bar Screen Package Control Systems shall
a. Multi-rake Bar Screen 1 Control Panel LCP854341.
b. Multi-rake Bar Screen 2 Control Panel LCP854342.
Control Panels. ▇▇▇▇▇-▇▇▇▇▇▇▇ PLC CompactLogic Racks, Each Rack to include:
Control Panels. 3.15.4.1 Panels shall be provided for control and monitoring of the machine and shall be sized to take environmental conditions into account. The panel shall be dust & water splash tight & the ambient temperature outside may go up to 45 deg. C. The IP level for the control panel shall be at least IP55.
3.15.4.2 All panels shall be designed to accommodate ambient temperature and humidity conditions, by having heating cum air conditioning systems of reputed international makes only.
3.15.4.3 The design shall suitably consider all aspects, which shall be discussed and tested during design stages. In addition the panels shall have the following:- -It shall have an earthing terminal. -It shall comply with the regulations in force. -The front panel shall be fitted with three indicating lights for the three incoming phases of power supply, lit when power on. -All the control panels should include special button for testing mode. -A three-pole isolating switch pad lockable in the open position will supply power to the installation. -Doors will have removable keys and compartments for storage of electrical diagrams. -Material for cabinet shall be metallic anticorrosion and painted / powder coated. -Wire marking must be engraved type. -The Contractor shall provide galvanic insulation between the different components. The electronic blocks and boards must be quickly replaceable without requiring dismantling of any other neither component nor removal of a cable or set of cables. -The sub-assemblies performing the same function shall be strictly identical and interchangeable. -The design of the electronics shall be such as to facilitate troubleshooting. In particular, for the technical boards: -the functions shall be distributed on boards connected to the cabling by connectors, this distribution shall be designed so as to limit the troubleshooting time (each function clearly delimited per board), The cabinet shall comprise: -a main three-pole isolating switch which can be padlocked in the open position, fitted each with high rupturing capacity (HRC) fuses and single- phasing preventer, -a main circuit breaker, -an isolating switch for each component, -the contactors and relays used for operation of the installation, -magnetic/thermal protection specific to each movement, -a programmable logic controller (type and brand to be specified),the transformer shall be designed with protection as per European standard EN 60204,the 415 V/230 V transformer (lighting, PLC or relay...
Control Panels a) The scope of work covers the plinth preparation for the installation of the control panels: 1800(H) x 2700(W) x 900(D) mm 1 item Section 3.2.9 R - 1800(H) x 600(W) x 600(D) mm 1 item Section 3.2.9 R - b) The scope of work covers the installation of the pre-assembled control panels: 2000(H) X 1600(W) X 800(D) mm 1 item Section 3.2.10 R - 1800(H) X 800(W) X 600(D) mm 3 item Section 3.2.10 R - 2000(H) X 800(W) X 800(D) mm 4 item Section 3.2.10 R - R - c) The scope of work covers the terminal wiring of incoming cable for the following control panels as per Works Information: incl. earthing of spare cores. Unit * Main Unit Controller Local 300 item Section 3.2.13 and 3.2.14;Appendix E figure 6, 7, 8 and 9 R - Unit * Main Unit Controller Remote IO Generator 300 item Section 3.2.13 and 3.2.14;Appendix E figure 6, 7, 8 and 9 R - Unit * Main Unit Controller Remote IO Turbine 350 item Section 3.2.13 and 3.2.14;Appendix E figure 6, 7, 8 and 9 R - Unit * Main Unit Controller Remote IO Common 200 item Section 3.2.13 and 3.2.14;Appendix E figure 6, 7, 8 and 9 R - Unit * Digital Governor 100 item Section 3.2.13 and 3.2.14;Appendix E figure 6, 7, 8 and 9 R - Unit * Temperature and Speed Monitoring 300 item Section 3.2.13 and 3.2.14;Appendix E figure 6, 7, 8 and 9 R - National Control Centre interface 50 item Section 3.2.13 and 3.2.14;Appendix E figure 6, 7, 8 and 9 R - Station Controller 0 item Section 3.2.13 and 3.2.14;Appendix E figure 6, 7, 8 and 9 R - Station Remote IO 0 item Section 3.2.13 and 3.2.14;▇▇▇▇▇▇▇▇ E figure 6, 7, 8 and 9 R - R -
Control Panels. Lamps should be provided to indicate running and tripped conditions, normal and fault conditions, pressurisation unit fault, frost thermostat operation etc. as appropriate to indicate the status of all plant being controlled via the panel. These lamps shall be LED type and coloured green for normal or run status, and red for fail or fault status. Further information about lamp colours may be found in BSEN 60204-1:2018. Panel indicator lamps shall be ▇▇▇▇▇▇▇▇▇ Electric, Harmony LED series XB4, 24v AC for control circuits, 240v ac Mains.
Control Panels. 2.9.1 MyAccount
Control Panels a) The scope of contract covers the dismantle and removals of components and control cubicles of the following panels diamension: 1800(H) x 2700(W) x 900(D) mm 1 item Section 3.2.5 R - 1800(H) x 2400(W) x 600(D) mm 1 item Section 3.2.5 R - 1395(H) x 900(W) x 550(D) mm 3 item Section 3.2.5 R - 1800(H) x 600(W) x 600(D) mm 1 item Section 3.2.5 R - R -
Control Panels. A. All control panels, factory, shop or field assembled, shall be labeled as a unit in accordance with UL 508. The UL 508 label shall be affixed to the inside of the door or cover, adjacent to the data pocket.